Permit Number: T06CM01710
Parcel: 11005327C

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T06CM01710
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/28/2006 MICHAEL ST. PAUL ZONING REVIEW Approved
03/28/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied The minimum insulation for ducts located in unconditioned spaces within the building envelope is R-5 (installed). Reference Section 803.2.8, IECC 2003.
03/28/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide the listing information for the proposed 2-way cleanout. Reference sections 707.4 and 707.6, UPC 2003.
2. Provide a detail of the water heater re-installation, including the excess pressure relief (including size, route, and termination) expansion tank, and valves. Reference Sections 103.2.3, 605.5, and 608.3 UPC 2003.
3. Show that the position stops on the mixing valves for the showers are to be adjusted to supply a maximum water temperature of 120 degrees Fahrenheit.
03/28/2006 ROBERT SHERRY WATER REVIEW Approved
03/28/2006 MARTIN BROWN FIRE REVIEW Approved
03/28/2006 PATRICIA GILBERT ENGINEERING REVIEW Approved
03/29/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved
04/04/2006 CAGUILA1 WWM REVIEW Needs Review
04/04/2006 CAGUILA1 BUILDING-COMMERCIAL REVIEW Needs Review