Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T06CM01696
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/13/2007 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL. PLEASE CALL AT 791-5550 X1106 OR EMAIL AT Linda.Buczynski@tucsonaz.gov IF YOU CARE TO DISCUSS. 1. Bathrooms shall have a 20A circuit, not a 15A. Reference NEC 210.11 (C) (3). 2. Small appliance branch circuit receptacles shall serve no other outlets per NEC 210.52 (B) (2). This effects Circuit 13. 3. It appears that the bar needs another receptacle per NEC 210.52 (C) (1). 4. Site lighting and irrigation circuits may not be powered from the panels which supply the dwelling unit electrical loads. Reference NEC 210.25. |
| 03/22/2007 | DAVID RIVERA | ZONING | REVIEW | Denied | the building plans cannot be approved until the site plan is approved. |
| 04/02/2007 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 04/02/2007 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 04/09/2007 | PATRICIA GILBERT | ENGINEERING | REVIEW | Denied | An approved site plan is required prior to building plan approval. |
| 04/25/2007 | LINHART PETERSEN POERS ASSOC. | BUILDING-COMMERCIAL | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 05/04/2007 | GERARDO BONILLA | OUT TO CUSTOMER | Completed |
| 05/04/2007 | SUE REEVES | REJECT SHELF | Completed |