Permit Number: T06CM01696
Parcel: 13707035U

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T06CM01696
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/13/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1106 OR EMAIL AT Linda.Buczynski@tucsonaz.gov
IF YOU CARE TO DISCUSS.

1. Bathrooms shall have a 20A circuit, not a 15A. Reference NEC 210.11 (C) (3).
2. Small appliance branch circuit receptacles shall serve no other outlets per NEC 210.52 (B) (2). This effects Circuit 13.
3. It appears that the bar needs another receptacle per NEC 210.52 (C) (1).
4. Site lighting and irrigation circuits may not be powered from the panels which supply the dwelling unit electrical loads. Reference NEC 210.25.
03/22/2007 DAVID RIVERA ZONING REVIEW Denied the building plans cannot be approved until the site plan is approved.
04/02/2007 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
04/02/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
04/09/2007 PATRICIA GILBERT ENGINEERING REVIEW Denied An approved site plan is required prior to building plan approval.
04/25/2007 LINHART PETERSEN POERS ASSOC. BUILDING-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
05/04/2007 GERARDO BONILLA OUT TO CUSTOMER Completed
05/04/2007 SUE REEVES REJECT SHELF Completed