Permit Number: T06CM01690
Parcel: 136321320

Review Status: Completed

Review Details: RESIDENTIAL BLDG/WWM

Permit Number - T06CM01690
Review Name: RESIDENTIAL BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/02/2006 ADRIAN ALEGRIA BUILDING-RESIDENTIAL REVIEW Denied PLAN REVIEW COMMENTS for Activity # T06CM01690

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, highlighting any changes, along with a written response to each of the noted items indicating action taken.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2003 International Residential Code, 2003 International Energy Conservation Code, and Arizona State amendments to the 2003 Uniform Plumbing Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

GENERAL REQUIREMENTS:

All corrections and revisions shall be made on original tracings or finished reproducible set. Return this set and a copy along with a set of the first submission. Pen or pencil corrections on final prints will not be acceptable. To avoid delays, ensure that all corrections have been made, are complete, and have been coordinated on all applicable detail and note sheets.

All engineers and architects involved in the design of the structure are to seal the related sheets of plans, details and calculations in accordance with the rules of the State Board of Technical Registration.

Construction drawing guidelines are available from the residential desk of the Development Services Division.

As of 9-02-04 the City of Tucson has adopted the 2003 IRC with the exception of the plumbing portion which has been replaced with the 2003 UPC with amendments. All model plans shall reference these codes.
All code references to the International Residential Code shall be changed from 2000 to 2003 with appropriate paragraph references.
Correct illegible overtyped statements:
All dimensions and notes shall be consistent on each plan or elevation.
Provide a note for: Underground facility tracer wires per DSD Memo, 10/24/2005.

FOUNDATION PLANS:

· Show the minimum 12" footing depth below undisturbed soil, R403.1.4. Verify footing detail 1 on sheet D1, according with the scale proposed.

ELEVATIONS:

· Note and size all roofing drains and scuppers for flat roofed areas, R903.4.

PLUMBING PLANS:

· The City of Tucson has adopted the 2003 Uniform Plumbing Code with state amendments (ARIZONA STATE PLUMBING CODE). The plans should reference this code.
· Provide the length of line to each gas appliance (water heater), BTU demand of each appliance, size of each branch, total demand, and total developed length from meter to the most remote appliance on the system, UPC 1217.0 & Table 12-7. (water heater)

MECHANICAL PLANS:

· Appliances installed in garages shall be mounted on platforms at least 18" above the floor, M1307.3.

OUTDOOR LIGHTING CODE

· Full cut-off fixtures have no emittance above the nadir (no deco openings, semi-opaque panels or exposed lamps). Fixtures may be exempt from the total lumen budget if both of the full cut-off FCO style and located under overhangs, OLC 5.1.2. Provide cut sheets for all FCO fixtures showing the angle of cutoff, light emissions and fixture wattage. All other fixtures are assumed to be unshielded (non-FCO style). Fixtures may be considered FCO if the installed lamp does not extend below the fixture shielding.
· Provide lamp data for all FCO fixtures Show compliance with City of Tucson Outdoor Lighting Code; the unshielded limit for area E3 is 12,000 lumens per acre., E3a is 9,000 lumens per acre. Include all exterior fixtures on the property in the calculations. Review guidance: www.ci.tucson.az.us/dsd/Codes___Ordinances/Tucson_Lighting_Code.pdf

· Proposed: 9071sq.ft. / 43560 = 0.2082
· E3 unshielded lumens 12,000 x 0.2082 = 2498 lumens allowable
· Fixture quantity 5 with 75 Watts each 1040 lumens
· 5 x 1040 = 5200
· 2498 lumens allowable < 5200 unshielded lumens proposed

If you have any questions, please contact your assigned plans examiner Adrian Alegria at 791-5550, extension 1186.