Permit Review Detail
Review Status: Completed
Review Details: OTHER
Permit Number - T06CM01671
Review Name: OTHER
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/25/2007 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | 1. THE RISER DIAGRAM ON REVISION SHOWS TWO 600 AMP SERVICES, ACCORDING TO FIELD INSPECTIONS,THE INSTALLED SERVICES ARE 800 AMP, PLEASE VERIFY AND IF SO CORRECT ON DRAWING. ON FIRST PLAN ONE SERVICE IS SHOWN TO BE 800 AMP. 2.EACH SERVICE SHOWS ONE OVERHEAD FEED FROM UTILITY AS 4 #500 MCM CONDUCTORS ONLY , THEY APPEAR TO BE THE ONLY CONDUCTORS GOING THUR THE WEATHERHEAD DOWN THE 3" CONDUIT TO THE SERVICE ENCLOSURE. THE AMPACITY FOR 500MCM COPPER IS SHOWN TO BE 380 AMPS, THE LOAD SHOWN IS 536 AMPS ON SERVICE A-A, AND 581 AMPS FOR SERVICE A-B. I PRESUME THESE WILL BE PARALLED FEEDS HOWEVER THEY NEED TO BE DRAWN ON PLAN. THE PARALLEL FEEDS MY ALSO CHANGE THE SHORT CIRCUIT CALCULATION PLEASE REVIEW. 3. THE OVERHEAD FEED FROM THE UTILITY TRANSFORMERS DO NOT CARRY A FOURTH WIRE PLEASE CLARIFY THIS |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 07/27/2007 | VFLORES1 | OUT TO CUSTOMER | Completed |