Permit Number: T06CM01620
Parcel: 13312068G

Review Status: Completed

Review Details: SITE

Permit Number - T06CM01620
Review Name: SITE
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/24/2006 MARTIN BROWN FIRE REVIEW Denied Fire hydrant required.
03/29/2006 PETER MCLAUGHLIN NPPO REVIEW Denied Submit NPP plan or Application for Exception; If submitting an Application for an NPPO Exception, include acceptable documentation, which clearly indicates that the project will not impact Protected Native Plants. Such documentation includes photographs of the site taken from all sides of the property. Photographs of the site are necessary for NPPO approval per DS 2-15.2.0.C
03/29/2006 PETER MCLAUGHLIN LANDSCAPE REVIEW Denied 1) Revise the landscape plan to include all screening elements in accordance with LUC Table 3.7.2-I. The southernmost portion of the site near east property line must be screened from the adjacent residentially zoned property to the east with a 5-foot wall. Note the height and type of material/construction of all screen walls.

2) Dimension all landscape areas, including the parking lot planter areas (both elongated planters within the interior parking lot area and the triangular planters adjacent to the parking spaces along the east property line) on the landscape plan drawing. An unpaved planting area, which is a minimum of thirty-four (34) square feet in area and four (4) feet in width, must be provided for each canopy tree.
DS 2-07.2.2.A.2.e, LUC 3.7.2.3.A.1.c

3) Regarding MS&R right-of-way, show existing and future dimensions of Wrightstown Road along with any utility locations. DS 2-05.2.4.D.2

4) Add the existing and future sight-visibility triangles (SVTs) to the landscape plan. LUC 3.7.2.8 & DS 2-06

5) Refer to DS 2-07.2.2.B and DS 2-06.5.4 for the specific content for Grading Information required on the landscape plan. Grading information on the landscape plan shall include contour lines or spot elevations for the site, percent slope across the site and direction of slope of paved areas, as is provided on the site plan.
04/19/2006 PAUL MACHADO ENGINEERING REVIEW Denied To: GDA Southwest, Inc. DATE: April 26, 2006
Architects
250 S. Craycroft Rd., Ste. 200
Tucson, Arizona 85711
SUBJECT: 7670 E. Wrightwtown Rd.
Site plan T06CM01620 (First Review)
T14S, R15E, Section 05

RESUBMITTAL REQUIRED: Site Plan and Hydrology Report.

The Site Plan (SP) and Hydrology Report (HR) cannot be approved as submitted. Please address the following review comments prior to the next submittal.

Site Plan:

1. Please include a response letter to the comments along with the corrected copies of the SP.
2. Please label lot dimensions and bearings per D.S. 2-02.2.1.5
3. Include details on the plans of all the depressed landscape areas used for retention including size and depth.
4. Label existing and future sight visibility triangles per D.S. 2-02.2.1.10.
5. Show all points of egress and ingress including locations and width of driveways and parking area access lanes (P.A.A.L.) per D.S. 2-02.2.1.11.
6. Please label all vehicular, bicycle, pedestrian, and handicapped circulation clearly identified per D.S. 2-02.2.1.12.
7. Fully dimensioned loading space(s) and maneuvering area(s) per D.S. 2-02.2.1.14.
8. Show the limits of the 100-year floodplain and water surface elevation per D.S. 2-02.2.1.15.
9. Please provide Drainage patterns and finished grades per D.S. 2-02.2.1.16.
10. Please list estimated cut & fill quantities per D.S. 2-02.2.1.17.
11. Please show dimensioned right-of-way, including any applicable Major Streets and Routes (MS&R) Plan right-of-way per D.S. 2-02.2.1.19.
12. All easement of record must be graphically shown on the plan together with recording docket and page per D.S. 2-02.2.1.20.
13. Add the basin(s) maintenance responsibility note per S.M.D.D.F.M. 2.3.1.6 C 1 and 2 to the SP.
14. Dimension from street monument lines to existing and proposed curbs, sidewalks, driveways, and utility lines per D.S. 2-02.2.1.21.
15. Please provide existing topographic contours at intervals not exceeding two (2) feet and/or spot elevations as pertinent per D.S. 2-02.2.1.23. Label the contour lines with the elevations and call out the C.I. next to the scale.
16. Show Site plan number (T06CM01620) on all sheets per D.S. 2-02.2.1.29.
17. Show refuse container location, size, and access thereto fully dimensioned per D.S. 2-02.2.1.32 and D.S. 6-01.0. The service truck must reverse in a straight line. The refuse enclose shown does not allow for the 40' straight back up with out encroaching into the parking spaces. Also the service vehicle cannot turn into the aisle after servicing the enclosure due to the
18. Placement of fill in excess of 2' above existing grade at any location in the outer 100' of the developing site is not allowed and/or shall meet the requirements per D.S. 11-01. Please address.
19. A permit or a private improvement agreement will be necessary for any work performed within the Right-of-way. Contact Permits and Codes at (520) 791-5100 for permit information.
20. Please show a typical cross section of the P.A.A.L. or call out the percentage of slopes. Call out the GB at the D/W, if applicable.
21. Please show the proposed roof drainage patterns, 100% of the 10-year flow must be conveyed under the sidewalks including any other site drainage as well. Please provide supporting calculations to demonstrate compliance with D.S. 3-01.4.4. If the location(s) of the roof scuppers have not yet been decided, a general note indicating sidewalk scuppers will be used when the roof scuppers locations have been designed and located will suffice.
22. List the consulting engineer and the owner/developer on the plans with the pertinent information.
23. Add note: "Depress all landscaped areas 6" maximum for water harvesting".
24. "A grading permit and Stormwater Pollution Prevention Plans (SWPPP's) will be required for this project. Submit 4 sets of grading and SWPPP's with text, upon completion and submittal of a grading permit application. A grading permit may not be issued prior to site plan approval. Subsequent comments may be necessary, depending upon the nature and extent of revisions that occur to the plans".

Hydrology Report:
1. Please include a response letter to the comments along with the corrected copies of the HR.
2. Include an exhibit in the HR showing all the depressed landscape areas used for retention including size and depth.
3. All depressed landscaped areas used for retention shall be tested for percolation rates and the results submitted with the HR prior to grading approval.
4. Add the basin(s) maintenance responsibility note and checklist per S.M.D.D.F.M. 2.3.1.6 C 1 and 2 to the HR.

If you have any questions, I can be reached at 791-5550 x1193 or Paul.Machado@tucsonaz.gov
Paul P. Machado
Senior Engineering Associate
City of Tucson/Development Services Department
201 N. Stone Avenue
P.O. Box 27210
Tucson, Arizona 85726-7210
(520) 791-5550 x1193 office
(520) 879-8010 fax
C:/7670 E. Wrightwtown RD Site
05/23/2006 HEATHER THRALL ZONING HC SITE REVIEW Denied See zoning comments
05/23/2006 HEATHER THRALL ZONING REVIEW Denied TO: Development Services Department Plans Coordination Office

FROM: Heather Thrall
Senior Planner

PROJECT: T06CM01620
7670 E. Wrightstown Road
Gymnastics Academy, Instructional School
Site plan

TRANSMITTAL DATE: May 22, 2006

COMMENTS: Please resubmit revised drawings along with redlines and a response letter, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.

1. This project was reviewed for compliance with requirements of the Land Use Code (LUC), Development Standard (DS), American National Standard Institute (ANSI), and International Building Code 2003 (IBC). Specifically, site plan content was reviewed for compliance with DS 2-02. This project was reviewed as an instructional school.

2. Per DS 2-02.2.1.4, list recorded subdivisions with docket/page on/next to location map.

3. Per DS 2-02.2.1.5, call out clear lot dimensions and bearings.

4. Per DS 2-02.2.1.8, with regards to parking
A) provide angle of parking spaces
B) dimension all aspects of all parking spaces per LUC 3.3.7.2. chart
C) provide floor plan of building to ensure parking ratio is correct
D) provide parking bumpers along north parking row to prevent vehicles overhanging into landscaping
E) note, a potential maneuvering problem for a sanitation vehicle is seen between the dumpster and the parking space to the north/west side of the vehicle. See Engineering notes and be aware further maneuvering demonstration may be needed.

5. PAAL width will be reviewed for the angled parking upon resubmittal to ensure the correct PAAL width is given depending upon the angle of the parking space. Provide directional arrows.

6. Per DS 2-02.2.1.12 and DS 2-08, clarify if the area between the angled parking and the building is entirely concrete - pedestrian/handicapped access connections from the sidewalk to the ramps need to be clearly noted please.

Clarify if the area between the striped pedestrian refuge and the handicapped ramp adjacent to the building is flush with the concrete, otherwise, the ramp will have to be moved to ensure handicapped access to the sidewalk surrounding the building.

7. Per DS 2-02.2.1.19, please clarify the location of the future curb along Wrightstown Road. In addition, the Major Streets and Routes Map lists Wrightstown as having a total right of way in the future of 120 feet. The plan submitted indicates an 81' right of way for current and future. Clarify - is this half right of way in reference? Correct if not.

8. Per DS 2-02.2.1.20, show any easements with recordation information on the plan.

9. Per DS 2-02.2.1.21, show any proposed free-standing lighting with specs on the plan.

10. Per DS 2-02.2.2.A.2, clarify the provided lot size, versus the lot size listed in the Floor Area Ratio calculation. Check and revise as necessary.

11. All uses in the C-1 zone are subject to LUC 2.5.3.6.A (drive through limits) and B (outdoor activities). This project, in particular, will be more subject to LUC 2.5.3.6. B. Please place the following note on the site plan in the code review section "This project is subject to LUC 2.5.3.6.B, all land use activities except vehicular use areas shall be conducted entirely within an enclosed building unless specifically provided otherwise."

12. Depending upon the responses provided, further review comments may be forthcoming. Should you have any questions on this review, contact me at Heather.Thrall@tucsonaz.gov or at 791-4541x1156.


If you have any questions about this transmittal, please call (520) 791-5608.

HCT C:\planning\site\DSD\T06CM01620 7670 e wrightstown.doc

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised site plan and additional requested documents

Final Status

Task End Date Reviewer's Name Type of Review Description
05/26/2006 ADRIANNE OLIVO OUT TO CUSTOMER Completed
05/26/2006 SUE REEVES REJECT SHELF Completed