Review Date Reviewer's Name Type of Review Description Status Comments
06/29/2006 DAVE MANN FIRE REVIEW Approved
06/29/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Provide balancing information (i.e. air flow rates) for the air conditioning system and the restroom exhaust.
06/29/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved
06/29/2006 ROBERT SHERRY WATER REVIEW Approved
06/29/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Only a direct-vented water heater may be installed in a restroom. Reference Section 303.3, IFGC 2003.
06/30/2006 GBONILL1 WWM REVIEW Needs Review
06/30/2006 GBONILL1 BUILDING-COMMERCIAL REVIEW Needs Review
06/30/2006 GBONILL1 ENGINEERING REVIEW Needs Review
06/30/2006 GBONILL1 ZONING REVIEW Needs Review
06/30/2006 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review