Permit Number: T06CM01600
Parcel: 13205015V

Address:
3450 E 36TH ST

Review Status: Completed

Review Details: COMMERCIAL-BLDG/FIRE/ZONING/ENG

Permit Number - T06CM01600
Review Name: COMMERCIAL-BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/22/2006 GBONILL1 ZONING REVIEW Needs Review
05/22/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved T06CM01600 5/12/06

1. Registrant's seal is not legible.
2. Grounding connection to existing water pipe has to be sized per Table 250.66 and total cross sectional area of derived conductors. Two 4/0 have a total cross-sectional area of 433200 cmil. The #4 should be 1/0.
05/26/2006 SREEVES1 BUILDING-COMMERCIAL REVIEW Passed passed per D Mann for modular. State review