| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/22/2006 | GBONILL1 | ZONING | REVIEW | Needs Review | |
| 05/22/2006 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | T06CM01600 5/12/06 1. Registrant's seal is not legible. 2. Grounding connection to existing water pipe has to be sized per Table 250.66 and total cross sectional area of derived conductors. Two 4/0 have a total cross-sectional area of 433200 cmil. The #4 should be 1/0. |
| 05/26/2006 | SREEVES1 | BUILDING-COMMERCIAL | REVIEW | Passed | passed per D Mann for modular. State review |