Permit Number: T06CM01600
Parcel: 13205015V

Address:
3450 E 36TH ST

Review Status: Completed

Review Details: COMMERCIAL-BLDG/FIRE/ZONING/ENG

Permit Number - T06CM01600
Review Name: COMMERCIAL-BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/24/2006 SUZANNE BOHNET ENGINEERING REVIEW Approved
05/08/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T06CM01600 5/8/06

1. Clarify panel and circuits which are intended to power the Compressors. Provide load calculations. Clarify nature of facility. What sort of industrial process take place here, and do the compressors/related equipment get installed in an area which should be Classified?
2. Provide load calculations for Existing MCC.
3. Provide sizes for the fuses in the New Office Addition disconnects.
4. Provide Available fault current at service, fault calculations, and fault current rating of all new equipment.
5. Provide sizing for the Grounding Electrode Conductor to Existing Ground and Water Pipe.
05/12/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
05/12/2006 AKLAPPE1 BUILDING-COMMERCIAL REVIEW Needs Review
05/12/2006 AKLAPPE1 ZONING REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
05/12/2006 AMERY KLAPPERT OUT TO CUSTOMER Completed