| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/24/2006 | SUZANNE BOHNET | ENGINEERING | REVIEW | Approved | |
| 05/08/2006 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T06CM01600 5/8/06 1. Clarify panel and circuits which are intended to power the Compressors. Provide load calculations. Clarify nature of facility. What sort of industrial process take place here, and do the compressors/related equipment get installed in an area which should be Classified? 2. Provide load calculations for Existing MCC. 3. Provide sizes for the fuses in the New Office Addition disconnects. 4. Provide Available fault current at service, fault calculations, and fault current rating of all new equipment. 5. Provide sizing for the Grounding Electrode Conductor to Existing Ground and Water Pipe. |
| 05/12/2006 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 05/12/2006 | AKLAPPE1 | BUILDING-COMMERCIAL | REVIEW | Needs Review | |
| 05/12/2006 | AKLAPPE1 | ZONING | REVIEW | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 05/12/2006 | AMERY KLAPPERT | OUT TO CUSTOMER | Completed |