| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/22/2006 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 03/29/2006 | PETER MCLAUGHLIN | NPPO | REVIEW | Denied | Submit NPP plan or Application for Exception; If submitting an Application for an NPP Exception, include acceptable documentation, which clearly indicates that the project will not impact Protected Native Plants. Such documentation includes photographs of the site taken from all sides of the property. Photographs of the site are necessary for NPPO approval per DS 2-15.2.0.C |
| 03/29/2006 | PETER MCLAUGHLIN | LANDSCAPE | REVIEW | Denied | 1) This proposal is being reviewed as a change of use with full code compliance required per LUC 3.7.1.2.A.. 2) Submit a separate landscape plan per DS 2-07.0. to verify that entire site will meet current minimum requirements, and to be able to accurately determine what issues will require Board of Adjustment Variances. DS 2-02.2.1.C 3) Provide a legal description of the property on the landscape plan. DS 2-07.2.1.B 4) Refer to DS 2-06 for Landscaping and Screening Standards and to DS 2-07.2.2 for all required elements of proposed landscaping and screening improvements to be shown on the landscape plan, including planting plan, calculations, screening, maintenance schedule, grading information, irrigation plan, construction details, etc. Further comments will apply once a landscape plan is submitted. 5) Both the proper and common name of each type of plant material must be listed. Locations, size, and name of all existing vegetation to remain in place. Material and areas of inert ground cover. All disturbed areas including adjacent right of ways shall be treated with ground cover such as decomposed granite to help reduce dust pollution per LUC 3.7.2.7. Indicate treatment for landscaped areas. 6) Landscape plan shall include irrigation specification design and layout per DS 2-07.5.4.A & DS 2-07.5.4.B including source of irrigation, sleeves for driveways and sidewalks, locations of valves, low-flow bubblers or drip irrigation. 7) Indicate square footage of all landscaped areas and provide a calculation of the percentage of vegetative coverage on the landscape plan per DS 2-07.2.2.2.g. Fifty (50) percent or more of the street landscape border area must have shrubs and vegetative ground cover per LUC 3.7.2.4 8) A 6' wall is required for screening of the loading area from adjacent properties per LUC Table 3.7.2-I. Identify the wall location on the landscape plan. Specify the height of the wall and indicate its type of material/construction on the landscape plan. 9) Street landscape borders shall be a minimum of ten (10) feet wide as measured from the street property line, and located entirely on site. Written approval from the City Engineer is required to allow landscaping in the right-of-way per LUC 3.7.2.4.A.3 and landscape improvements proposed in public right-of-way areas must be approved by the City Engineer or designee and comply with the City Engineer's requirements on construction, irrigation, location, and plant type. Provide verification, in writing, of any approvals obtained. Contact Gary Wittwer, DOT Landscape Architect at (520) 791-5100 for specific requirements. 10) All lettering and dimensions must be a minimum of 12 point (0.12") in size for microfilming purposes. Revise any text which does not meet this minimum archiving standard. DS2-03.2.1.C 11) Provide specific information about what plants are proposed on the site by using a legend with symbols unique to each plant. 12) On the landscape plan indicate the methods by which water harvesting or storm water runoff is used to benefit planting areas on the site. LUC 3.7.4.3.B 13) It is apparent that Board of Adjustment variances will be required for the proposed change of use development. If approved, add the Board of Adjustment case number reference number, date of approval, what variances were approved for, and any conditions imposed to the plan as required. DS 2-07.2.1.B.2.c DS 2-07.2.1 14) Some of the locations of the plants on the submitted site plan are shown to be on concrete curbs or in the adjacent alleyway. Show the location of all plants correctly. Trees planted near sidewalks, curbs or other paved areas shall be planted at a sufficient distance to prevent pavement upheaval. Where the distance is not available or where the design places the trees closer to the surfaced improvements, suitable barriers to the root system to mitigate pavement upheaval or soil settling will be installed with the landscaping. If the trees are in the public right-of-way, the root barriers must be approved by the City Engineer or designee. Under no circumstances shall grading encroach to the base or trunk of a native tree. DS 2-063.5.E DS 2-15.6.0.A 15) The precise location of the 5-foot wall is unclear on the plan. There are labels along the property line which indicate an existing fence/new 5-foot CMU wall. Show the exact location of fences and walls separately (indicate where the perimeter wall stops and the fence begins) on the landscape plan. State the height and materials of any fencing to remain. Note that per LUC TABLE 3.7.2-I, a 5-foot masonry wall is required as a screen for the adjacent R-2 zoned property to the east. 16) Revise the north arrow to be correct. DS 2-02.2.1.A.1 17) Add a location map per DS 2-02.2.1.A.4 18) Additional comments may be required up submittal of Landscape plan and NPP plan. |
| 04/15/2006 | PATRICIA GILBERT | ENGINEERING | REVIEW | Denied | DATE: April 15, 2006 ACTIVITY NUMBER: T06CM01580 PROJECT NAME: Gravina Law Offices PROJECT ADDRESS: 3546 North Euclid Avenue PROJECT REVIEWER: Patricia Gilbert, Engineering Associate The following items must be revised or added to the site plan. Please include a response letter with the next submittal that states how all comments have been addressed. RESUBMITTAL REQUIRED: SITE PLAN 1. Provide a north arrow. DS 2-02.2.1.A.1. 2. Provide a location map. DS 2-02.2.1.A.4. 3. Add a legend to the plan indicating different line type, shading, etc. 4. Provide bearings for each lot dimension. DS 2-02.2.1.A.5. 5. Label the length of the sight distance for the existing sight visibility triangles. DS 2-02.2.1.A.10. 6. Provide SVT's for the ingress/egress for the PAAL to the alley. DS 2-02.2.1.A.10. 7. Provide drainage patterns and proposed finish grades. DS 2-02.2.1.A.16. 8. Include on the site plan estimated cut and fill quantities. If cut and fill quantities equal zero, please note on the plan. DS 2-02.2.1.A.17. 9. Provide the book and page for Euclid Avenue. Indicate if Euclid Ave. is a public or private road. DS 2-02.2.1.A.18. 10. Dimension from the street centerline of Euclid Avenue to the existing curb, existing or proposed sidewalk and utility lines. DS 2-02.2.1.A.21. 11. Provide existing topographic contours at intervals not exceeding 2' and/or spot elevations as pertinent and indicate the Bench Mark based on the City of Tucson Datum, include City book and page number. DS 2-02.2.1.A.23. 12. New projects will provide centralized on-site refuse storage, collection and pickup areas. Indicate refuse container location, size and access thereto fully dimensioned. Demonstrate vehicle maneuverability fully dimensioned. Refuse vehicles require 36' inside radius and 50' outside radius. Indicate a refuse enclosure detail as per D.S. 6-01.4.2 Contact John Clark of Environmental Services @ 791-3175 ext. 1136 to reach an alternative solution if the requirements in DS 6-01 can not be met. Any proposed solution not meeting DS 6-01, will required an approved Development Standard Modification Request (DSMR). 13. Alleys are to be used for utility placement, provision of sanitary services and as a secondary point of access for residential development. This project is utilizing the alley for primary access to the parking area located behind the building. Revise the site plan to show primary access off of Euclid Avenue or summit written approval from the Department of Transportation for primary use of the alley. Any alternative solution not meeting DS 3-01.6.6. must obtain a DSMR. 14. Street landscape borders must be located entirely on site unless the City Engineer approves 5' or less of the required landscaping located within the ROW. Relocate the 10' landscape border or submit written approval from the City Engineer. LUC3.7.2.4.A.2. |
| 05/02/2006 | HEATHER THRALL | ZONING | REVIEW | Denied | TO: Development Services Department Plans Coordination Office FROM: Heather Thrall Senior Planner PROJECT: T06CM01580 3546 N. Euclid Avenue Proposed residence to commercial office conversion Site plan review TRANSMITTAL DATE: May 5, 2006 COMMENTS: Please resubmit revised drawings along with redlines and a response letter, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed. 1. This plan was reviewed for requirements of the Land Use Code (LUC), Development Standard (DS), American National Standard Institute (ANSI) and International Building Code 2003 (IBC). Specifically, this plan was reviewed for compliance with site plan content requirements of DS 2-02. NOTE: This project is a change of use from residential to commercial, with the remodel of the residence to a commercial office use - which requires full code compliance. Please note, structural building code review staff should be consulted immediately on the feasibility and process of the conversion of the building use. Staff acknowledges intended variance notations are listed throughout the plan. Staff advises, prior to resubmittal, the best attempt to redesign the project should be made to avoid variances. All review comments must be addressed, and variance referral comments will be issued once only variance issues remain. To acknowledge your variance notes, a (V) symbol is placed next to the related review comment. 2. For record keeping needs, please enlarge all type face to 12 point at minimum. 3. Per DS 2-02.2.1.2, add the legal description to the plan. 4. Per DS 2-02.2.1.4, add a location map (meeting criteria of 2-05.2.1.D) to the plan. 5. Per DS 2-02.2.1.5, add bearings to all lot lines. 6. Per DS 2-02.2.1.6, provide a note on the plan the project consists of the conversion of a residence to an office. IF THIS SITE IS TO BE BOTH RESIDENTIAL AND COMMERCIAL OFFICE, CODE REQUIREMENTS FOR BOTH USES MUST BE MET ON THE SITE. Please clarify. NOTE: if the use of the site is only for an office, THE EXISTING KITCHEN SHOWN ON THE PLANS SHOULD BE LABELED AS "TO BE REMOVED". 7. Per DS 2-02.2.1.7/LUC 2.4.3.2, the required minimum setback for an office building use in the O-3 zone abutting an adjacent R-2 zone is equal to 1.5 times the height of the exterior building wall. The south property line setback is insufficient. Please respond how this issue will be addressed. 8. Per DS 2-02.2.1.8/DS 3-05/LUC 3.3.4, RE: parking, please provide: A) dimension distance between front of parking spaces and front of wheel stop B) demonstrate vehicular maneuverability/exiting for the handicapped parking space C) clarifying location of carport poles D) call out the distance between handicapped parking space and building wall adjacent E) (V) insufficient parking spaces are provided, 10 spaces required for use F) identify location of handicapped parking signage and provide sign/fine details 9. Per DS 2-02.2.1.9/LUC 3.3.4, provide bicycle parking location, number and specs. 10. Per DS 2-02.2.1.11/DS3-05, RE: Parking Area Access Lanes (PAAL) A) dimension PAAL at east side B) (V) alley access is not permitted C) (V) PAAL width at Euclid entrance is insufficient 11. Per DS 2-02.2.1.12/DS 2-08, a sidewalk should be provided from the east parking lot around the building to allow pedestrian access to the provided entrance at the west side. 12. Per DS 2-02.2.1.12/ANSI, RE: handicapped access: A) provide a handicapped ramp from handicapped parking space to sidewalk B) provide detail drawing with specs for handicapped ramp. C) Provide ramp with early detectable warnings (truncated domes). D) Provide a dimension from the west building wall face to the porch post - to ensure unimpeded pedestrian/handicapped access. E) See structural review with regards to positioning of the front swinging door for handicapped access requirements. F) See parking comment number 8 and ensure handicapped access signs provided 13. Per DS 2-02.2.1.13, Provide specs for any proposed free-standing signage. 14. Per DS 2-02.2.1.14, (V) Provide 1 loading space at 12x35, per LUC 3.4.5.5. 15. Per DS 2-02. 2.1.19, Provide recordation information for easement within Euclid. 16. Per DS 2-02.2.1.25, Provide note clarifying whether any free-standing lighting is proposed, and provide applicable dimensions/heights. 17. Per DS 2-02.2.2.A.1/2/3, list gross and net lot area, and floor area ratio. 18. Please provide a legend for any symbols used on the plan. 19. Depending upon the responses provided, further review comments may be forthcoming. Should you have any questions on this review, please contact me via email at Heather.Thrall@tucsonaz.gov or at 791-4541x1156. If you have any questions about this transmittal, please call (520) 791-5608x1156. HCT C:\planning\site\DSD\T06CM01580 3546 n euclid.doc RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised site plan and additional requested documents |
| 05/08/2006 | HEATHER THRALL | ZONING HC SITE | REVIEW | Denied | Please see zoning review comments. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 05/08/2006 | SUE REEVES | REJECT SHELF | RECEIVED |