Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T06CM01545
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/27/2006 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T06CM01545 3/27/06 NEXT REVIEW MAY BE DONE OVER THE COUNTER M-F 8:00-9:30. 1. Please note that the City of Tucson does not allow the "Up-Over-Down" method to attenuate fault current. Therefore, it appears that the AFC at New Panel D is a bit over 24,000A. If the Contractor chooses this option, this panel would not have sufficent fault current protection. 2. Load calculations are no longer a Code issue, but it appears that the Load Summary should total 733A, not 704. Tallys for each panel have been lightly pencilled in for reference. A correction would give the Owner a better sense of spare capacity on his service. |
| 03/30/2006 | AOLIVO1 | WWM | REVIEW | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 03/30/2006 | ADRIANNE OLIVO | OUT TO CUSTOMER | Completed |