| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/21/2006 | HEATHER THRALL | ZONING | REVIEW | Approved | |
| 03/21/2006 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Specify the capacity of the refrigeration equipment used for the walk-in cooler. |
| 03/21/2006 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T06CM01545 3/21/06 1. Panel A Phase B appears to total 22107 VA, not 20385. Amps for entire panel 163.1A, not 158.2. 2. Panel C Phases A, B, and C appear to total 26848, 26063, and 20541 VA, not 23323, 24413, and 19046 VA, respectively. Amps for entire panel 204.1A, not 185. Phases A and B appear to be overloaded. 3. Load summary appears to total 806.9A, not 784.7, overloading the 800A Existing Service Section. 4. Provide feeder sizes for all circuits exceeding 20A. 5. Circuits B-15 and B-17 are shown as separate receptacles on Sheet E2. 2-pole Enduro on Panel Schedule. Pls clarify. 6. ICEE on Panels C and D appear to draw 65A, exceeding the 30A circuit. 7. Plot location of electrical service on scaled drawing. 8. Provide fault calculations for Panel D. |
| 03/21/2006 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 03/21/2006 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Specify the backflow devices to be used for the new equipment. 2. Provide traps for the indirect waste lines that are over 5' in length. Run the indirect waste lines independently. |
| 03/21/2006 | SUZANNE BOHNET | ENGINEERING | REVIEW | Needs Review | |
| 03/22/2006 | GBONILL1 | BUILDING-COMMERCIAL | REVIEW | Denied | |
| 03/22/2006 | GBONILL1 | WWM | REVIEW | Needs Review | |
| 03/22/2006 | GBONILL1 | FIRE | REVIEW | Needs Review |