Permit Number: T06CM01545
Parcel: 11808002S

Address:
655 W 22ND ST

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T06CM01545
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/21/2006 HEATHER THRALL ZONING REVIEW Approved
03/21/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Specify the capacity of the refrigeration equipment used for the walk-in cooler.
03/21/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T06CM01545 3/21/06

1. Panel A Phase B appears to total 22107 VA, not 20385. Amps for entire panel 163.1A, not 158.2.
2. Panel C Phases A, B, and C appear to total 26848, 26063, and 20541 VA, not 23323, 24413, and 19046 VA, respectively. Amps for entire panel 204.1A, not 185. Phases A and B appear to be overloaded.
3. Load summary appears to total 806.9A, not 784.7, overloading the 800A Existing Service Section.
4. Provide feeder sizes for all circuits exceeding 20A.
5. Circuits B-15 and B-17 are shown as separate receptacles on Sheet E2. 2-pole Enduro on Panel Schedule. Pls clarify.
6. ICEE on Panels C and D appear to draw 65A, exceeding the 30A circuit.
7. Plot location of electrical service on scaled drawing.
8. Provide fault calculations for Panel D.
03/21/2006 ROBERT SHERRY WATER REVIEW Approved
03/21/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Specify the backflow devices to be used for the new equipment.
2. Provide traps for the indirect waste lines that are over 5' in length. Run the indirect waste lines independently.
03/21/2006 SUZANNE BOHNET ENGINEERING REVIEW Needs Review
03/22/2006 GBONILL1 BUILDING-COMMERCIAL REVIEW Denied
03/22/2006 GBONILL1 WWM REVIEW Needs Review
03/22/2006 GBONILL1 FIRE REVIEW Needs Review