Permit Number: T06CM01512
Parcel: 10511061R

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T06CM01512
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/04/2006 DOUG LAAKSO BUILDING-COMMERCIAL REVIEW Denied S1. SEE PRIOR COMMENT S3. (S3. PROVIDE STRUCTURAL DESIGN AND DETAILS FOR STOREFRONT INCLUDING FASTENER TYPE SIZE SPACING/NUMBER AND ATTACHMENT TO EXISTING STRUCTURE, SPECIFY MATERIALS .)
S2. SEE PRIOR COMMENT S4. ( S4.FULLY DIMENSION TOILET ROOM INCLUDING SIDE WALL TO LAV OF 60" MIN PER ANSI A117.1-2003ed.)
S3. SEE PRIOR COMMENT S5. ( S5. ADDRESS OVERAL ACCESSIBILITY FOR EXISTING BUILDING 20% REQUIRED TO BE SPENT ON ACCESSIBILTY, PROVIDE ESTIMATE ON DRAWINGS PER 2003 IBC CHAPTER 11 AND 34 AND ANSI A117.1.)
S4. SEE PRIOR COMMENT S6. (S6. CLARIFY EXITING AND OCCUPANT LOADS FOR SPACES/ ROOMS IF SECOND EXIT REQUIRED THROUGH STORAGE AREA PROVIDE CORRIDOR.)
04/04/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
04/04/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved