Permit Number: T06CM01512
Parcel: 10511061R

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T06CM01512
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/20/2006 SUZANNE BOHNET ENGINEERING REVIEW Approved
03/20/2006 GERRY KOZIOL WWM REVIEW Approved
03/20/2006 PETER MCLAUGHLIN ZONING REVIEW Approved
03/21/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide a riser diagram showing how the water, waste, and vent piping is to be modified.
2. Provide temperature controls for the lavatory per Section 414.1, UPC 2003 and Section 804.3, IECC 2003.
03/21/2006 DOUG LAAKSO BUILDING-COMMERCIAL REVIEW Denied S1. PROVIDE PROJECT VALUATION.
S2. USE CURRENT CODES SEE WEBSITE WWW.TUCSONAZ.GOV/DSD .
S3. PROVIDE STRUCTURAL DESIGN AND DETAILS FOR STOREFRONT INCLUDING FASTENER TYPE SIZE SPACING/NUMBER AND ATTACHMENT TO EXISTING STRUCTURE, SPECIFY MATERIALS .
S4. FULLY DIMENSION TOILET ROOM INCLUDING SIDE WALL TO LAV OF 60" MIN PER ANSI A117.1-2003ed.
S5.ADDRESS OVERAL ACCESSIBILITY FOR EXISTING BUILDING 20% REQUIRED TO BE SPENT ON ACCESSIBILTY, PROVIDE ESTIMATE ON DRAWINGS PER 2003 IBC CHAPTER 11 AND 34 AND ANSI A117.1.
S6. CLARIFY EXITING AND OCCUPANT LOADS FOR SPACES/ ROOMS IF SECOND EXIT REQUIRED THROUGH STORAGE AREA PROVIDE CORRIDOR.
S7. MINIMUM LETTER SIZE ON SUBMITTAL TO BE 1/8 INCH ALL CAPITALS.
S8. PROVIDE COMPLETED CODE REVIEW CHECKLIST.
03/21/2006 ROBERT SHERRY WATER REVIEW Approved
03/21/2006 MARTIN BROWN FIRE REVIEW Approved
03/21/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Revise the design of the HVAC for the restroom to prevent recirculation of the air supplied to the restroom. Reference Section 402.3.1(3), IMC 2003.
2. New ductwork and flexible duct shall have a minimum insulation of R-5 in unconditioned spaces.
04/04/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved T05CM01512 3/21/06

1. Sheet P.0 calls for a 3.5 KW 208V WH. Please provide electrical power.
2. City of Tucson currently enforces the 2003 IECC not 2001.
http://www.tucsonaz.gov/dsd/Codes___Ordinances/Building_Codes/building_codes.html.