Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 2ND
Permit Number - T06CM01510
Review Name: REVISION - - 2ND
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
10/17/2006 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
10/18/2006 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T06CM01510 10/18/06 1. Provide a circuit for the receptacles on the north side of the building, the ones that are not circuited. 2. Ckt A-23 is CU-1 on Power Plan. On panel schedule this is a receptacle load. Clarify. 3. A-25 is a receptacle load on Power Plan. This ia a space on the panel schedule. Clarify. 4. Ckt A-37 powers EF-1 on Power Plan. This circuit is a spare on the panel schedule. Clarify. 5. Fill in the electrical load for A-41 on the panel schedule. INCOMPLETE REVIEW. PLEASE PERFORM QUALITY CONTROL, THE SUBMIT PLANS. |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
10/24/2006 | CINDY AGUILAR | APPROVAL SHELF | Completed |
10/24/2006 | CINDY AGUILAR | OUT TO CUSTOMER | Completed |