Permit Number: T06CM01510
Parcel: 11505161B

Address:
2222 N STONE AV

Review Status: Completed

Review Details: REVISION - - 2ND

Permit Number - T06CM01510
Review Name: REVISION - - 2ND
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/17/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
10/18/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T06CM01510 10/18/06

1. Provide a circuit for the receptacles on the north side of the building, the ones that are not circuited.
2. Ckt A-23 is CU-1 on Power Plan. On panel schedule this is a receptacle load. Clarify.
3. A-25 is a receptacle load on Power Plan. This ia a space on the panel schedule. Clarify.
4. Ckt A-37 powers EF-1 on Power Plan. This circuit is a spare on the panel schedule. Clarify.
5. Fill in the electrical load for A-41 on the panel schedule.


INCOMPLETE REVIEW. PLEASE PERFORM QUALITY CONTROL, THE SUBMIT PLANS.

Final Status

Task End Date Reviewer's Name Type of Review Description
10/24/2006 CINDY AGUILAR APPROVAL SHELF Completed
10/24/2006 CINDY AGUILAR OUT TO CUSTOMER Completed