Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 1ST
Permit Number - T06CM01510
Review Name: REVISION - - 1ST
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/07/2006 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T06CM01510 8/7/06 1. Provide an electrical circuit for AH-1. 2. Provide the fusing required on Sheet M1 for CU1. 3. Panel is shown interior on Sheet E2. Panel schedule indicates that this in and Exterior panel. Please clarify. |
| 08/07/2006 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 08/07/2006 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 08/08/2006 | CINDY AGUILAR | APPROVAL SHELF | Completed |
| 08/08/2006 | CINDY AGUILAR | OUT TO CUSTOMER | Completed |