Permit Number: T06CM01510
Parcel: 11505161B

Address:
2222 N STONE AV

Review Status: Completed

Review Details: REVISION - - 1ST

Permit Number - T06CM01510
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/07/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T06CM01510 8/7/06

1. Provide an electrical circuit for AH-1.
2. Provide the fusing required on Sheet M1 for CU1.
3. Panel is shown interior on Sheet E2. Panel schedule indicates that this in and Exterior panel. Please clarify.
08/07/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
08/07/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
08/08/2006 CINDY AGUILAR APPROVAL SHELF Completed
08/08/2006 CINDY AGUILAR OUT TO CUSTOMER Completed