Permit Review Detail
Review Status: Completed
Review Details: POST 3RD PARTY REVIEW
Permit Number - T06CM01487
Review Name: POST 3RD PARTY REVIEW
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
10/16/2006 | ROBERT SHERRY | WATER | REVIEW | Passed | |
10/16/2006 | MARTIN BROWN | FIRE | REVIEW | Denied | Basement must have sprinklers per IFC 903.2.10.1. Please add the following automatic sprinkler criteria to the plans: 1. The hazard classification of the occupancy including any special hazards. 2. The design standard to be used. 3. The availability and adequacy of the water supply. 4. The design density and the area of operation. |
10/25/2006 | VFLORES1 | WWM | REVIEW | Needs Review | |
10/26/2006 | JASON GREEN | ENGINEERING | REVIEW | Needs Review | Building plans are not in the site plan package at the time engineering reviewed and approved the site plan. Building plans may still be at 3rd party review. Engineering approval of the building plans are still required. |
10/26/2006 | HEATHER THRALL | ZONING | REVIEW | Needs Review | building plans were not in the site plan package, and may still be at 3rd party review at the time zoning reviewed and approved the site plan. note that the building plans can be reviewed at the counter by zoning. only once the building plans are actually approved by 3rd party review is zoning able to approve the building plans. |
10/27/2006 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review |