Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T06CM01417
Parcel: 133231390

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T06CM01417
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/22/2006 DAVE MANN BUILDING-COMMERCIAL REVIEW Approved
03/22/2006 ROBERT SHERRY WATER REVIEW Approved
03/22/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Revise the fonts to be uppercase, a minimum of 1/8" high.
2. Provide a letter from Pima County Industrial Wastewater Control that approves the installation of the 3-compartment sink without a grease trap.
3. Clarify what is new and what is existingon sheet P1.1.
4. Provide a description of P-3.
03/22/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T06CM01417 3/22/06

1. Overcurrent protection for new freezer appears to be oversized. 12.1A should have 20A CB, not 40A. Reference NEC 422.11 (E). Unless 40A is marked on the appliance, please modify plans.
2. Please account for largest motor and continuous load for Panel A. Verify that the panel does not become overloaded.
3. Values do not correspond to those in the 2003 IECC. For example, Kitchen allows 1.2 W/SF, not 1.7, food prep is not a separate category, bathrooms, corridors and support areas are 0.9, not 0.8.
03/22/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Revise the fonts to be uppercase, a minimum of 1/8" high.
2. Show that the common ventilation complies with Section 403.3.2, IMC 2003.
3. Provide listing information for the existing hood to show that it is properly balanced.
03/29/2006 AOLIVO1 WWM REVIEW Needs Review