Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T06CM01414
Parcel: Unknown

Address:
7150 S TUCSON BL

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T06CM01414
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/15/2006 MARTIN BROWN FIRE REVIEW Approved
03/15/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
03/15/2006 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Denied 1) SHOW ACCESSIBLE RESTROOMS ON DRAWINGS.
03/15/2006 ROBERT SHERRY WATER REVIEW Approved
03/15/2006 TERRY STEVENS ZONING REVIEW Passed
03/15/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Show how the outside air quantities for the rooftop units were calculated.
2. Show the location of the new AC-A .
3. Show that the new exhaust fan and the existing plubing vents are at least 10 feet from any air intakes.
4. Revise the insulation for the new interior ductwork to have a minimum resistance of R5 per Section 803.2.8, IECC 2003.
03/15/2006 JOSE ORTIZ ENGINEERING REVIEW Approved
03/16/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Needs Review
03/17/2006 AOLIVO1 WWM REVIEW Needs Review