Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T06CM01414
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
03/15/2006 | MARTIN BROWN | FIRE | REVIEW | Approved | |
03/15/2006 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
03/15/2006 | CHRISTY FOREMAN | BUILDING-COMMERCIAL | REVIEW | Denied | 1) SHOW ACCESSIBLE RESTROOMS ON DRAWINGS. |
03/15/2006 | ROBERT SHERRY | WATER | REVIEW | Approved | |
03/15/2006 | TERRY STEVENS | ZONING | REVIEW | Passed | |
03/15/2006 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Show how the outside air quantities for the rooftop units were calculated. 2. Show the location of the new AC-A . 3. Show that the new exhaust fan and the existing plubing vents are at least 10 feet from any air intakes. 4. Revise the insulation for the new interior ductwork to have a minimum resistance of R5 per Section 803.2.8, IECC 2003. |
03/15/2006 | JOSE ORTIZ | ENGINEERING | REVIEW | Approved | |
03/16/2006 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review | |
03/17/2006 | AOLIVO1 | WWM | REVIEW | Needs Review |