04/06/2006 RAUL PALMA BUILDING-COMMERCIAL REVIEW Denied 1) Provide a detail showing how the existing CMU wall
footing and the post footing is constructed. Show any
rebar or dowals and spacing of them. Specify the size
of the existing ftg. Provide engieering calcs for this specific ftg.
2) Is the existing footing projecting into public way? Is
there a permit for the existing CMU wall? Verify!
3) Verify that existing 4x8 @ 36" o.c. spaning 16'-8" is o k.