Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL-BLDG/FIRE/ZONING/ENG
Permit Number - T06CM01409
Review Name: COMMERCIAL-BLDG/FIRE/ZONING/ENG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/06/2006 | RAUL PALMA | BUILDING-COMMERCIAL | REVIEW | Denied | 1) Provide a detail showing how the existing CMU wall footing and the post footing is constructed. Show any rebar or dowals and spacing of them. Specify the size of the existing ftg. Provide engieering calcs for this specific ftg. 2) Is the existing footing projecting into public way? Is there a permit for the existing CMU wall? Verify! 3) Verify that existing 4x8 @ 36" o.c. spaning 16'-8" is o k. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 04/11/2006 | ADRIANNE OLIVO | OUT TO CUSTOMER | Completed |
| 04/11/2006 | SUE REEVES | REJECT SHELF | Completed |