Permit Number: T06CM01399
Parcel: 12201024G

Address:
3926 E GRANT RD

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T06CM01399
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/14/2006 MARTIN BROWN FIRE REVIEW Approved
03/14/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Show how the water temperature to the lavatories is to be limited to a maximum of 120 F. Reference Section 414.1, UPC 2003.
03/14/2006 RAUL PALMA BUILDING-COMMERCIAL REVIEW Approved
03/14/2006 ROBERT SHERRY WATER REVIEW Approved
03/14/2006 HEATHER THRALL ZONING REVIEW Approved
03/14/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
03/14/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved t06cm01399 3/14/06

It appears that the circuiting on the exit lights are not in compliance with NEC 700.12 (E). The branch circuit feeding this unit equipment shall be the same as that serving the normal lighting in the area.
03/14/2006 JOSE ORTIZ ENGINEERING REVIEW Approved
03/15/2006 AOLIVO1 WWM REVIEW Needs Review