Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T06CM01399
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/14/2006 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 03/14/2006 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Show how the water temperature to the lavatories is to be limited to a maximum of 120 F. Reference Section 414.1, UPC 2003. |
| 03/14/2006 | RAUL PALMA | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 03/14/2006 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 03/14/2006 | HEATHER THRALL | ZONING | REVIEW | Approved | |
| 03/14/2006 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 03/14/2006 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | t06cm01399 3/14/06 It appears that the circuiting on the exit lights are not in compliance with NEC 700.12 (E). The branch circuit feeding this unit equipment shall be the same as that serving the normal lighting in the area. |
| 03/14/2006 | JOSE ORTIZ | ENGINEERING | REVIEW | Approved | |
| 03/15/2006 | AOLIVO1 | WWM | REVIEW | Needs Review |