Permit Number: T06CM01380
Parcel: 122173860

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T06CM01380
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/13/2006 MARTIN BROWN FIRE REVIEW Approved
03/14/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Provide additional information (e.g. a riser diagram) to show how the waste piping is to be modified.
03/14/2006 TERRY STEVENS ZONING REVIEW Approved
03/14/2006 ROBERT SHERRY WATER REVIEW Approved
03/14/2006 SUZANNE BOHNET ENGINEERING REVIEW Approved
03/14/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
03/22/2006 GBONILL1 BUILDING-COMMERCIAL REVIEW Needs Review
03/22/2006 GBONILL1 WWM REVIEW Needs Review
03/22/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved T06CM01380 3/14/06

1. Ckts A-13 and A-15 power lights. They are spares on the panel schedule. Pls clarify.
2. It appears that Ckts A-10 and A-12 should count at 720VA, not 360 and 540.
3. Single Line Riser Keynote 7 panel A is new. The panel is existing according to the panel schedule.
4. Single Line Riser Keynote 8 panel B is existing. The panel is new according to the panel schedule.
5. Single Line Keynote 2 200AF shall not protect a 100A panel.
6. Single Line Keynote C #2 is of ampacity 115A, and load of 134A exceeds this.
7. Provide available fault current at service.
8. Provide fault calculations for new panel(s).