| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/13/2006 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 03/14/2006 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Provide additional information (e.g. a riser diagram) to show how the waste piping is to be modified. |
| 03/14/2006 | TERRY STEVENS | ZONING | REVIEW | Approved | |
| 03/14/2006 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 03/14/2006 | SUZANNE BOHNET | ENGINEERING | REVIEW | Approved | |
| 03/14/2006 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 03/22/2006 | GBONILL1 | BUILDING-COMMERCIAL | REVIEW | Needs Review | |
| 03/22/2006 | GBONILL1 | WWM | REVIEW | Needs Review | |
| 03/22/2006 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | T06CM01380 3/14/06 1. Ckts A-13 and A-15 power lights. They are spares on the panel schedule. Pls clarify. 2. It appears that Ckts A-10 and A-12 should count at 720VA, not 360 and 540. 3. Single Line Riser Keynote 7 panel A is new. The panel is existing according to the panel schedule. 4. Single Line Riser Keynote 8 panel B is existing. The panel is new according to the panel schedule. 5. Single Line Keynote 2 200AF shall not protect a 100A panel. 6. Single Line Keynote C #2 is of ampacity 115A, and load of 134A exceeds this. 7. Provide available fault current at service. 8. Provide fault calculations for new panel(s). |