Parcel: 131090620

Review Status: Completed

Review Details: RESIDENTIAL BLDG/WWM

Permit Number - T06CM01371
Review Name: RESIDENTIAL BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/17/2006 ANDREW CONNOR NPPO REVIEW Passed
04/12/2006 WILDAN 2ND PARTY REVIEW REVIEW Denied April 12, 2006

City of Tucson Development Services
201 N. Stone Ave.
Tucson, AZ 85701

RE: 24th STREET DUPLEX – 1ST REVIEW
CITY OF TUCSON LOG NO. T06CM01371
WILLDAN PROJECT NO. 13881-6016

The initial review for the above project has been completed. This letter contains comments which need to be addressed by written responses to each which indicate any actions taken. In order to facilitate a shorter second review, all corrections and revisions must be made on the original plans and two complete new sets of prints, along with one complete redlined set, must be returned to our office. To avoid delays, ensure that all corrections have been made, are complete, and have been coordinated on all applicable detail and note sheets, and that all changes have been highlighted with appropriate revision numbers, revision dates, and “cloud bubbles.” Pen or pencil corrections on final prints are not acceptable.

This project has been reviewed for conformance with the 2003 IRC, 1997 UAC, 2003 IMC, 2003 IECC, 2002 NEC codes with local modifications, and the 2003 UPC with State of Arizona Amendments. Any revisions to this plan will require an additional review and approval by Willdan.

Should you have questions regarding the comments herein, please contact your plans examiner Antonio Moya.

Occupancy Occup. Load Construction Area S.F. Sprinklered Alarms
Dwelling
Porch N/A V/B 1970
472 No Smoke

Special Inspection is required for the following items:
N/A

The following items are acceptable for deferred submittals:
N/A

GENERAL COMMENTS:
N/A

ARCHITECTURAL COMMENTS:
Reviewed and accepted.

STRUCTURAL COMMENTS:
Reviewed and accepted.

PLUMBING COMMENTS:
Sheet P-1
On the vent and drainage for the washer and dryer there are penetrations on the fire-rated wall that need to comply with a fire step penetration system and fire resistance assembly. Also the membrane penetration should maintain its fire-rated resistance. Reference UPC Sections 317.3.1.1, 317.3.1.2, 317.3.2.

MECHANICAL COMMENTS:
Reviewed and accepted.

ELECTRICAL COMMENTS:
Sheet E-1
The bedrooms are on the same circuit as the dining room. Please correct. Reference IRC Sections E3603.2, E3801.3.1.

Note on plans: “All branch circuits that supply 125-volt, single-phase, 15- and 2-ampere outlets installed in dwelling unit bedrooms shall be protected by an arc-fault circuit interrupter listed to provide protection for the entire branch circuit.” Reference IRC Section E3802.11.

Please provide cut sheets for all the exterior light fixtures and fans shown or noted on the plans. The cut sheets need to provide lumens per fixture and show if the fixture is a full cut-off, which means no light is emitted at or above the horizontal plane. If necessary, please revise calculations. Reference City of Tucson Outdoor Lighting Code.

Cross-reference fixtures on plans with the cut sheets and calculations.

The 1545-08 Bisque wall light is not a shielded fixture because it emits light above the horizontal plane.

ENERGY CODE COMMENTS:
Sheet P-1
Provide a note that water heaters with vertical pipe risers shall have a heat trap on both the inlet and outlet of the water h eater, unless the water heater has an integral heat trap or is part of a circulating system. Reference IECC Section 504.9.

ACCESSIBILITY COMMENTS:
Reviewed and accepted.


Sincerely,

WILLDAN




Martin Haeberle, C.B.O.
Building Official

MAH/ri
04/13/2006 GERRY KOZIOL WWM REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
04/24/2006 AMERY KLAPPERT OUT TO CUSTOMER Completed
04/24/2006 SUE REEVES REJECT SHELF Completed