Permit Number: T06CM01349
Parcel: 12510006B

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T06CM01349
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/02/2006 RAUL PALMA BUILDING-COMMERCIAL REVIEW Approved
05/05/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Keynote #7 calls for the removal of specific existing natural gas piping but the piping does not appear on the mechanical plan.
05/05/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Clarify what is being done with the roof top unit being relocated from K-6 to somewhere off the sheet. Reference Section 106.3.1, IMC 2003.
2. Keynote #3 calls for the removal of an existing evaporative cooler but the cooler does not appear on the mechanical plan.
3. Clarify the termination points of the new condensate drains; are they terminating in an area capable of absorbing the condensate flow without surface flow? Reference Section 307.2.1, IMC 2003, as amended by the City of Tucson.
4. What is the basis for the quantities of outside air being supplied to the relocated rooftop units? Reference Section 403, IMC 2005