Permit Number: T06CM01346
Parcel: 12701005D

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T06CM01346
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/09/2006 MARTIN BROWN FIRE REVIEW Approved
03/09/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
03/09/2006 RAUL PALMA BUILDING-COMMERCIAL REVIEW Approved
03/09/2006 ROBERT SHERRY WATER REVIEW Approved
03/09/2006 SUZANNE BOHNET ENGINEERING REVIEW Approved
03/09/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
03/13/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved T06CM01346 3/9/06

1. please provide for the grounding of the telephone system. Reference NEC 800.40.
2. Please demonstrate that no phase of Panel EBP2 is overloaded.
3. Please demonstrate that distribution panel feeding Panel EBP is not overloaded. It has an 800A OCPD, but 1600A total sub-feeders.
03/13/2006 GERRY KOZIOL WWM REVIEW Passed
03/13/2006 HEATHER THRALL ZONING REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
03/21/2006 GBONILL1 APPROVAL SHELF Completed
03/21/2006 GBONILL1 OUT TO CUSTOMER Completed