Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T06CM01346
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/09/2006 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 03/09/2006 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
| 03/09/2006 | RAUL PALMA | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 03/09/2006 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 03/09/2006 | SUZANNE BOHNET | ENGINEERING | REVIEW | Approved | |
| 03/09/2006 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 03/13/2006 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | T06CM01346 3/9/06 1. please provide for the grounding of the telephone system. Reference NEC 800.40. 2. Please demonstrate that no phase of Panel EBP2 is overloaded. 3. Please demonstrate that distribution panel feeding Panel EBP is not overloaded. It has an 800A OCPD, but 1600A total sub-feeders. |
| 03/13/2006 | GERRY KOZIOL | WWM | REVIEW | Passed | |
| 03/13/2006 | HEATHER THRALL | ZONING | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 03/21/2006 | GBONILL1 | APPROVAL SHELF | Completed |
| 03/21/2006 | GBONILL1 | OUT TO CUSTOMER | Completed |