Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T06CM01328
Parcel: 12701005D

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T06CM01328
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/08/2006 MARTIN BROWN FIRE REVIEW Approved
03/08/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
03/08/2006 DOUG LAAKSO BUILDING-COMMERCIAL REVIEW Approved
03/08/2006 GERRY KOZIOL WWM REVIEW Passed
03/08/2006 TERRY STEVENS ZONING REVIEW Approved
03/08/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
03/08/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved
03/08/2006 ROBERT SHERRY WATER REVIEW Approved
03/08/2006 SUZANNE BOHNET ENGINEERING REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
03/21/2006 GBONILL1 OUT TO CUSTOMER Completed