| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/31/2006 | SREEVES1 | WATER | REVIEW | Passed | APPROVED LAST WORKFLOW |
| 04/03/2006 | BOB SUBA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | Electrical Plans Reviewer Bob Suba indicated that review comments are on permit card. |
| 04/24/2006 | CHRISTY FOREMAN | BUILDING-COMMERCIAL | REVIEW | Denied | CITY OF TUCSON DEVELOPMENT SERVICES STRUCTURAL REVIEW COMMENTS DATE: 4/24/06 ACTIVITY NUMBER: T06CM01313 PROJECT NAME: T.I. HOME DEPOT PROJECT ADDRESS: 1155 IRVINGTON RD. ARCHITECT / ENGINEER: ARCHITECTURAL GROUP INTERNATIONAL PROJECT REVIEWER: CHRISTY FOREMAN TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL. PLEASE CALL AT 791-5550 X1108 OR EMAIL AT CFOREMA1@CI.TUCSON.AZ.US IF YOU CARE TO DISCUSS. 1) REVIEWED LETTER ADDRESSED TO MR. LAAKSO. THE CITY OF TUCSON OBSERVES THE 2003 IBC THEREFORE ITEMS SHALL BE ADDRESSED PER THE ANSI A117.1 2003. PLEASE NOTE ON DRAWING THAT ACCESSIBILITY IS FULLY COMPLIANT WITH ANSI A117.1 2003 OR ADDRESS CHAPT. 34 SECTION 3409.6 EXCEPTION 1. 2) STRUCTURAL CALCULATIONS PROVIDED ARE FOR THE WRONG LOCATION. CALCULATIONS ARE FOR STORE #0469 IN MESA, AZ. THIS STORE IS 467 IN TUCSON, AZ. 3) CLARIFY STRUCTURAL CALCULATION PROVIDED ARE PER SECTION 2208, 2003 IBC. |