Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T06CM01289
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/06/2006 | SUZANNE BOHNET | ENGINEERING | REVIEW | Approved | |
| 03/07/2006 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide riser diagramsfor the water and the waste & vent. 2. Add upper terminal cleanouts and a 2-1/2" cleanout where the drain increases to 3". 3. Adjust the water and waste fixture units per Tables 6-4 and 7-3, UPC 2003. 4. Provide insulation for the first 8' of CW and HW piping at the water heater. 5. Correct the water pressure calculations. |
| 03/07/2006 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 03/07/2006 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Revise the restroom ventilation to prevent recirculation of air from the restrooms. |
| 03/08/2006 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 03/09/2006 | HEATHER THRALL | ZONING | REVIEW | Approved | |
| 03/10/2006 | CHRISTY FOREMAN | BUILDING-COMMERCIAL | REVIEW | Needs Review | |
| 03/21/2006 | JMORALE1 | WWM | REVIEW | Needs Review | |
| 03/21/2006 | JMORALE1 | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review |