Permit Number: T06CM01289
Parcel: 13322471B

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T06CM01289
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/06/2006 SUZANNE BOHNET ENGINEERING REVIEW Approved
03/07/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide riser diagramsfor the water and the waste & vent.
2. Add upper terminal cleanouts and a 2-1/2" cleanout where the drain increases to 3".
3. Adjust the water and waste fixture units per Tables 6-4 and 7-3, UPC 2003.
4. Provide insulation for the first 8' of CW and HW piping at the water heater.
5. Correct the water pressure calculations.
03/07/2006 ROBERT SHERRY WATER REVIEW Approved
03/07/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Revise the restroom ventilation to prevent recirculation of air from the restrooms.
03/08/2006 MARTIN BROWN FIRE REVIEW Approved
03/09/2006 HEATHER THRALL ZONING REVIEW Approved
03/10/2006 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Needs Review
03/21/2006 JMORALE1 WWM REVIEW Needs Review
03/21/2006 JMORALE1 ELECTRICAL-COMMERCIAL REVIEW Needs Review