Permit Number: T06CM01263
Parcel: 13018001B

Address:
3940 E 29TH ST

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T06CM01263
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/03/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Revise the design of the natural gas piping to include the load of all of the connected appliances. (The heating value of the local supply of natural gas is approximately 1000 btu/cubic foot.)
2. Provide an automatic shut off valve for the gas pipe serving the appliances located under the hood.
3. If corrugated stainless steel gas piping is to be used, provide calculations to show that it is properly sized.
03/03/2006 ROBERT SHERRY WATER REVIEW Approved
03/03/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide a COMPLETE design for the installation of the Type I hood, grease duct, exhaust fan, and make up air system. Show how your design complies with all of the code requirements.
2. Provide structural details and calculations to show that the hood is adequately supported from the stucture.
3. Any shop drawings of the hood shall be included in the drawing set and shall have been reviewed by an Arizona Registrant.
4. Provide 18" clearance from combustible structures per Section 507.7, IMC 2003.
03/24/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved
04/12/2006 GERRY KOZIOL WWM REVIEW Passed
04/12/2006 MARTIN BROWN FIRE REVIEW Approved
05/03/2006 AKLAPPE1 BUILDING-COMMERCIAL REVIEW Needs Review
05/03/2006 AKLAPPE1 ZONING REVIEW Needs Review
05/03/2006 AKLAPPE1 ENGINEERING REVIEW Needs Review