Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T06CM01263
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/03/2006 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Revise the design of the natural gas piping to include the load of all of the connected appliances. (The heating value of the local supply of natural gas is approximately 1000 btu/cubic foot.) 2. Provide an automatic shut off valve for the gas pipe serving the appliances located under the hood. 3. If corrugated stainless steel gas piping is to be used, provide calculations to show that it is properly sized. |
| 03/03/2006 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 03/03/2006 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Provide a COMPLETE design for the installation of the Type I hood, grease duct, exhaust fan, and make up air system. Show how your design complies with all of the code requirements. 2. Provide structural details and calculations to show that the hood is adequately supported from the stucture. 3. Any shop drawings of the hood shall be included in the drawing set and shall have been reviewed by an Arizona Registrant. 4. Provide 18" clearance from combustible structures per Section 507.7, IMC 2003. |
| 03/24/2006 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 04/12/2006 | GERRY KOZIOL | WWM | REVIEW | Passed | |
| 04/12/2006 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 05/03/2006 | AKLAPPE1 | BUILDING-COMMERCIAL | REVIEW | Needs Review | |
| 05/03/2006 | AKLAPPE1 | ZONING | REVIEW | Needs Review | |
| 05/03/2006 | AKLAPPE1 | ENGINEERING | REVIEW | Needs Review |