Permit Number: T06CM01236
Parcel: 137055230

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T06CM01236
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/12/2006 MARTIN BROWN FIRE REVIEW Approved
05/15/2006 BOB SUBA ELECTRICAL-COMMERCIAL REVIEW Approved
05/19/2006 GERRY KOZIOL WWM REVIEW Approved
05/30/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Justify the use of 3" traps for the 8 floor sinks being installed in this project. Reference Section 702.0 and footnotes 1 and 7 of Table 7-3, UPC 2003.
2. Revise the design of the vents shown in detail 2/M1 the requirements of Table 7-5, UPC 2003 for the maximum number of connected fixture units.
05/30/2006 ROBERT SHERRY WATER REVIEW Approved
05/30/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
06/09/2006 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Denied 1) Permit cannot be released until expired permits are cleared. See T01CM01503 - Store Fixtures and Shelves. This permit will need to be re-submitted,reviewed, and purchased per the 2003 IBC.

Final Status

Task End Date Reviewer's Name Type of Review Description
06/14/2006 ADRIANNE OLIVO OUT TO CUSTOMER Completed
06/14/2006 SUE REEVES REJECT SHELF Completed