Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T06CM01198
Parcel: 10511040D

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T06CM01198
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/01/2006 MARTIN BROWN FIRE REVIEW Approved
03/01/2006 MICHAEL ST. PAUL ZONING REVIEW Approved
03/01/2006 SUZANNE BOHNET ENGINEERING REVIEW Approved
03/02/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
03/02/2006 RAUL PALMA BUILDING-COMMERCIAL REVIEW Needs Review
03/02/2006 ROBERT SHERRY WATER REVIEW Approved
03/02/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Needs Review T06CM01198 3/2/06

1. Please justify only counting 360VA per work station in this salon. With the use of blow dryers and such, the load may be much larger.
2. It appears that the panel loading for Ckt 3 neglects the existing fixtures and exhaust fan, SW corner.
3. WH 12 KW 208 V single phase draws 57.7A. See Sheet P1.1. #8 ampacity is only 50A.
4. 12 KW WH is under counted on panel schedule. Coordinate with Plumbing and clarify.
5. Demonstrate compliance with the 2003 IECC with the addition of the track lights.
6. The note by the Partial Line Diagram refers to Panel PSG. No such panel this project.
03/02/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
03/03/2006 GERRY KOZIOL WWM REVIEW Passed