Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T06CM01198
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
03/01/2006 | MARTIN BROWN | FIRE | REVIEW | Approved | |
03/01/2006 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
03/01/2006 | SUZANNE BOHNET | ENGINEERING | REVIEW | Approved | |
03/02/2006 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
03/02/2006 | RAUL PALMA | BUILDING-COMMERCIAL | REVIEW | Needs Review | |
03/02/2006 | ROBERT SHERRY | WATER | REVIEW | Approved | |
03/02/2006 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review | T06CM01198 3/2/06 1. Please justify only counting 360VA per work station in this salon. With the use of blow dryers and such, the load may be much larger. 2. It appears that the panel loading for Ckt 3 neglects the existing fixtures and exhaust fan, SW corner. 3. WH 12 KW 208 V single phase draws 57.7A. See Sheet P1.1. #8 ampacity is only 50A. 4. 12 KW WH is under counted on panel schedule. Coordinate with Plumbing and clarify. 5. Demonstrate compliance with the 2003 IECC with the addition of the track lights. 6. The note by the Partial Line Diagram refers to Panel PSG. No such panel this project. |