03/01/2006 MARTIN BROWN FIRE REVIEW Approved
03/01/2006 MICHAEL ST. PAUL ZONING REVIEW Approved
03/01/2006 SUZANNE BOHNET ENGINEERING REVIEW Approved
03/02/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
03/02/2006 RAUL PALMA BUILDING-COMMERCIAL REVIEW Needs Review
03/02/2006 ROBERT SHERRY WATER REVIEW Approved
03/02/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Needs Review T06CM01198 3/2/06

1. Please justify only counting 360VA per work station in this salon. With the use of blow dryers and such, the load may be much larger.
2. It appears that the panel loading for Ckt 3 neglects the existing fixtures and exhaust fan, SW corner.
3. WH 12 KW 208 V single phase draws 57.7A. See Sheet P1.1. #8 ampacity is only 50A.
4. 12 KW WH is under counted on panel schedule. Coordinate with Plumbing and clarify.
5. Demonstrate compliance with the 2003 IECC with the addition of the track lights.
6. The note by the Partial Line Diagram refers to Panel PSG. No such panel this project.