Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T06CM01160
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/05/2006 | CHRISTY FOREMAN | BUILDING-COMMERCIAL | REVIEW | Denied | CITY OF TUCSON DEVELOPMENT SERVICES STRUCTURAL REVIEW COMMENTS DATE: 5/9/06 ACTIVITY NUMBER: T06CM01160 PROJECT NAME: JOHN WESLEY MILLER COMPANIES PROJECT ADDRESS: 63 E. CONGRESS ARCHITECT / ENGINEER: aba Architects PROJECT REVIEWER: Christy Foreman TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL. PLEASE CALL AT 791-5550 X1108 OR EMAIL AT CFOREMA1@CI.TUCSON.AZ.US IF YOU CARE TO DISCUSS. 1) 1997 Uniform Administrative Code - section 302.5 Inspection and Observation Program. When special inspection is required by Section 306, the architect or engineer of record shall prepare an inspection program which shall be submitted to the building official for approval prior to issuance of the building permit. The inspection program shall designate the portions of the work to have special inspection, the name or names of the individuals or firms who are to perform the special inspections and indicate the duties of the special inspectors. The special inspector shall be employed by the owner , the engineer or architect of record, or an agent of the owner, but not the contractor or any other person responsible for the work. When structural observation is required by Section 307, the inspection program shall name the individuals or firms who are to perform structural observation and describe the stages of construction at which structural observation is to occur. The inspection program shall include samples of inspection reports and provide time limits for submission of reports. 2) Justify 20% cost of construction being spent toward accessibility requirements per code section 3409.6 IBC 2003. Provide itemized breakdown of costs for items on the drawings. 3) Drinking fountain spout heights and water flow ANSI 602.4 and 602.6. or provide water cooler and show on plans. 4) It appears two permits are required. Existing was one space and demising wall creates two spaces. Official address slip required for each space. Or clarify use of large open space. 5) Clarify separated or non-separated use per 302.3.1 and 302.3.2 6) Change of occupancy address section 3406. 7) Include basement area in other permit set address section 1104.4. 8) Provide site plan showing accessible path from parking to bldg entrance per section 1105. 9) Epoxy anchors require special inspections. Special inspection form shall be submitted before permit will be released. 10) Clarify equation references for structural justification. Justify design for seismic. 11) Occupant load of 19 requires one accessible men's restroom and one accessible woman's restroom. 12) Dumbwaiter shaft justify per section 707. 13) Clarify location of solar panels. 14) Specify equipment loads for heat pumps on drawings. |
| 05/15/2006 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. All plans require a minimum of 1/8" type, all uppercase. Reference Section 103.2.3, UPC 2003. 2. Replot the plumbing drawings so that they are legible. Reference Section 103.2.3, UPC 2003. 3. Show how the temperature of the hot water supply to the public lavatories is controlled. Reference Section 414.1, UPC 2003 and Section 804.3, IECC 2003. 4. All storage-type water heaters require a listed expansion tank. Please show expansion tanks on plans. Reference Section 608.3, UPC 2003 with local amendments. 5. Show size, route and termination of T&P relief piping. Reference Section 608.5, UPC 2003. 6. If the specified water heater is not supplied with integral heat traps, provide heat traps on the supply and discharge piping. Reference Section 804.4, IECC 2003. 7. 5. If the specified water heater is not supplied with integral heat traps, provide 0.5" of insulation with a maximum conductivity of 0.27 btu per inch/h °F on the first 8 feet of supply and discharge piping. Reference Section 804.4, IECC 2003. |
| 05/15/2006 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Revise the font size used on the drawings to a minimum of 1/8-inch (all upper case). Reference Section 302.3, Uniform Administrative Code, 1997. 2. Replot the mechanical drawings so that they are legible. Reference Section 106.3.1, IMC 2003. 3. Provide the installed weight of the inside heat pump units and show how they are to be supported from the building structure. Reference Sections 106.3.1 and 302.1, IMC 2003. 4. Provide auxiliary drain pans or secondary drain systems for the inside heat pump units. Reference Section 307.2.3 IMC 2003. 5. Provide listing information for the specified flexible air duct and show that the design, sizing, and installation comply with the manufacturer's recommendations. Reference Sections 304.1, 603.2, and 603.6.1, IMC 2003. 6. The minimum insulation for ducts located in unconditioned spaces within the building envelope is R-5 (installed). Reference Section 803.2.8, IECC 2003. |
| 05/16/2006 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL. PLEASE CALL AT 791-5550 X1106 OR EMAIL AT Linda.Buczynski@tucsonaz.gov IF YOU CARE TO DISCUSS. 1. Provide a layout of all pieces of equipment in the photovoltaic system on a scaled drawing. 2. Place all photovoltaic information on same sized sheet as that of the rest of the project. 3. It is not clear where the actual DC disconnect is to be placed. If integral with the inverter, the location of this disconnect would violate the requirements of NEC 690.14 (C) (1). However, the 2005 Code allows this configuration in the case where the Exception to 690.14 (B) (1) is evoked. Please specify a metallic raceway for this application. 4. Specify the placards and provide the exact wording for the permanent plaque/directory required by NEC 690.56 (B) and 230.2 (E). |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 05/22/2006 | GBONILL1 | OUT TO CUSTOMER | Completed |
| 05/22/2006 | SUE REEVES | REJECT SHELF | Completed |