Permit Number: T06CM01160
Parcel: 117120210

Address:
63 E CONGRESS ST

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T06CM01160
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/28/2006 MARTIN BROWN FIRE REVIEW Approved
02/28/2006 MICHAEL ST. PAUL ZONING REVIEW Approved
02/28/2006 JOSE ORTIZ ENGINEERING REVIEW Approved
04/21/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Revise the drawing to provide legibility for the plan records.
2. Provide a detail of the water heater installation, including the excess pressure relief, expansion tank, and valves. Reference Sections 103.2.3, 605.5, and 608.3 UPC 2003.
3. All storage-type water heaters require a listed expansion tank. Please show expansion tanks on plans. Reference Section 608.3, UPC 2003 with local amendments.
4. If the specified water heater is not supplied with integral heat traps, provide heat traps on the supply and discharge piping. Reference Section 804.4, IECC 2003.
5. If the specified water heater is not supplied with integral heat traps, provide 0.5" of insulation with a maximum conductivity of 0.27 btu per inch/h °F on the first 8 feet of supply and discharge piping. Reference Section 804.4, IECC 2003.
6. Provide water supply isometrics. Reference Section 103.2.3, UPC 2003.
7. Show how the temperature of the hot water supply to the public lavatories is controlled. Reference Section 414.1, UPC 2003 and Section 804.3, IECC 2003.
04/21/2006 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Needs Review
04/21/2006 GERRY KOZIOL WWM REVIEW Approved
04/21/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T06CM01160 4/21/06

Please provide fault calculations for new panel. City does not allowed current limiting OCPD characteristics to limit fault current on panels.
04/21/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide the installed weight of the inside heat pump units and show how they are to be supported from the building structure. Reference Sections 106.3.1 and 302.1, IMC 2003.
2. Provide auxiliary drain pans or secondary drain systems for the inside heat pump units. Reference Section 307.2.3 IMC 2003.
3. Provide listing information for the specified flexible air duct and show that the design, sizing, and installation comply with the manufacturer's recommendations. Reference Sections 304.1, 603.2, and 603.6.1, IMC 2003.
4. The minimum insulation for ducts located in unconditioned spaces within the building envelope is R-5 (installed). Reference Section 803.2.8, IECC 2003.
04/21/2006 ROBERT SHERRY WATER REVIEW Approved