Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T06CM01094
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/05/2006 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 09/12/2006 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL. PLEASE CALL AT 791-5550 X1106 OR EMAIL AT Linda.Buczynski@tucsonaz.gov IF YOU CARE TO DISCUSS. PLEASE COMPLY WITH THE COMMENTS BELOW, AS INDICATED BY REVIEWER BOB SUBA DATED 5/6/06. 1) Define conductors copper or alum. for panel P4 feeders and HP-1 branch circuit conductors. This has not been specified on the plans. 2) Indicate the available fault current at the service, and provide fault calculations to demonstrate that the new panel is being installed within its rating. |
| 09/29/2006 | CHRISTY FOREMAN | BUILDING-COMMERCIAL | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 10/05/2006 | GERARDO BONILLA | APPROVAL SHELF | Completed |
| 10/05/2006 | GERARDO BONILLA | OUT TO CUSTOMER | Completed |
| 10/05/2006 | GERARDO BONILLA | REJECT SHELF | Completed |