Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T06CM01094
Parcel: 12106001B

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T06CM01094
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/05/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
09/12/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1106 OR EMAIL AT Linda.Buczynski@tucsonaz.gov
IF YOU CARE TO DISCUSS.

PLEASE COMPLY WITH THE COMMENTS BELOW, AS INDICATED BY REVIEWER BOB SUBA DATED 5/6/06.

1) Define conductors copper or alum. for panel P4 feeders and HP-1 branch circuit conductors. This has not been specified on the plans.
2) Indicate the available fault current at the service, and provide fault calculations to demonstrate that the new panel is being installed within its rating.
09/29/2006 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
10/05/2006 GERARDO BONILLA APPROVAL SHELF Completed
10/05/2006 GERARDO BONILLA OUT TO CUSTOMER Completed
10/05/2006 GERARDO BONILLA REJECT SHELF Completed