Permit Number: T06CM01094
Parcel: 12106001B

Review Status: Completed

Review Details: OTHER

Permit Number - T06CM01094
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/24/2006 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Denied CITY OF TUCSON DEVELOPMENT SERVICES
STRUCTURAL REVIEW COMMENTS

DATE: 4/24/06
ACTIVITY NUMBER: T06CM01094
PROJECT NAME: GOLD'S GYM NEW HEAT PUMP
PROJECT ADDRESS: 5851 E. SPEEDWAY
ARCHITECT / ENGINEER: BRENT WOODS
PROJECT REVIEWER: CHRISTY FOREMAN


TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1108 OR EMAIL AT CFOREMA1@CI.TUCSON.AZ.US IF YOU CARE TO DISCUSS.


1) IT APPEARS STRUCTURAL CALCULATIONS ARE MISSING TO JUSTIFY NEW DETAILS. CLARIFY LOADS AND EXISTING BEAMS CAN CARRY NEW LOADS.
2) CLARIFY ROOF FRAMING DIMENSIONS.
3) NOTE ON SHT S1.0, PAGE 1 SPECIFIES CLARIFICATION SHALL BE THROUGH ARCHITECT. THERE IS NO ARCHITECT OF RECORD ON THIS PROJECT.
4) IT APPEARS THESE DETAILS WERE NOT DRAWN FOR THIS PROJECT. A SIMPSON A35F WOOD CONNECTOR IS SPECIFIED AND THIS PROJECT SPECIFIES STEEL.
5)PROVIDE COPY OF CERTIFICATE OF OCCUPANCY FOR GOLD'S GYM.
05/02/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Clarify the relative locations and the extent of the work shown on the partial floor plan and the mechanical roof plan.
2. Clarify the outside air calculations. The calculations are based on 1200 square feet of "reception" but sheet G1.0 shows the work area to be 2000 square feet. Also, what is the actual use of the area?
05/04/2006 BOB SUBA ELECTRICAL-COMMERCIAL REVIEW Denied 1) define conductors copper or alum. for panel P4 feeders and HP-1 cir. conductors
2) indicate the available fault currnet

Final Status

Task End Date Reviewer's Name Type of Review Description
05/09/2006 DELMA ROBEY OUT TO CUSTOMER Completed