Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T06CM01094
Parcel: 12106001B

Review Status: Completed

Review Details: COMMERCIAL-BLDG/FIRE/ZONING/ENG

Permit Number - T06CM01094
Review Name: COMMERCIAL-BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/10/2006 JWILLIA5 BUILDING-COMMERCIAL REVIEW Needs Review
04/10/2006 DROBEY1 ELECTRICAL-COMMERCIAL REVIEW Needs Review
04/10/2006 DROBEY1 MECHANICAL-COMMERCIAL REVIEW Needs Review