Permit Number: T06CM01025
Parcel: 107020070

Review Status: Completed

Review Details: SITE

Permit Number - T06CM01025
Review Name: SITE
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/15/2006 JOE LINVILLE NPPO REVIEW Approved Exception.
03/15/2006 JOE LINVILLE LANDSCAPE REVIEW Denied Revise the landscape plan to provide trees for the new parking areas. LUC 3.7.2.3
03/31/2006 PATRICIA GILBERT ENGINEERING REVIEW Denied DATE: April 1, 2006
ACTIVITY NUMBER: T06CM01025
PROJECT NAME: Proposed Addition Long Meadow Ranch Property
PROJECT ADDRESS: 3248 North Freeway Industrial Loop
PROJECT REVIEWER: Patricia Gilbert, Engineering Associate

The following items must be revised or added to the site plan. Please include a response letter with the next submittal that states how all comments have been addressed.

RESUBMITTAL REQUIRED: SITE PLAN

1. Include on the site plan estimated cut and fill quantities. If cut and fill quantities equal zero, please note on the plan. DS 2-02.2.1.A.17.

2. Show roof drainage (flow arrows). DS 2-02.2.1.A.16.

3. Demonstrate vehicle maneuverability for the loading zone.

4. Handicap curb access ramps are required to be constructed with truncated domes, per recent a Federal ADA requirement. Show a detail or add a general note to the site plan indicating all public and private handicap curb access ramps will have truncated domes.
04/04/2006 CRAIG GROSS ZONING REVIEW Approved
04/05/2006 CRAIG GROSS ZONING HC SITE REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
04/06/2006 DELMA ROBEY OUT TO CUSTOMER Completed
04/06/2006 SUE REEVES REJECT SHELF Completed