Review Date Reviewer's Name Type of Review Description Status Comments
04/21/2006 GERRY KOZIOL WWM REVIEW Approved
04/24/2006 DANIEL RUSCH BUILDING-RESIDENTIAL REVIEW Denied PLAN REVIEW COMMENTS for Activity # T06CM01003

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, highlighting any changes, along with a written response to each of the noted items indicating action taken.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, model energy and electrical. All code references are to the 2003 International Residential Code, 2003 International Energy Conservation Code, and Arizona State amendments to the 2003 Uniform Plumbing Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

GENERAL REQUIREMENTS:

All corrections and revisions shall be made on original tracings or finished reproducible set. Return this set and a copy along with a set of the first submission. Pen or pencil corrections on final prints will not be acceptable. To avoid delays, ensure that all corrections have been made, are complete, and have been coordinated on all applicable detail and note sheets.

Construction drawing guidelines are available from the residential desk of the Development Services Division.

All code references to the International Residential Code shall be changed from 2000 to 2003 with appropriate paragraph references.
Correct illegible overtyped statements:
All dimensions and notes shall be consistent on each plan or elevation.
Provide a note for: Underground facility tracer wires per DSD Memo, 10/24/2005.

SITE PLAN: (NOT REQUIRED FOR MODEL PLANS)

1. Show the water pipe size from the meter to the building. The pipe must be sized for the calculated load, 2003 UPC 610.1. Include distance from meter.

FOUNDATION PLANS:

1 Show the 6" (4" veneer) minimum foundation height above finished grade, R404.1.6.
2. Show compliance with termite treatment specified by R320, as amended.
3. Indicate sill plate to treated lumber R 319
FLOOR PLANS:

1. Provide all window sizes and types, and designate the operable portion of windows, as well as the location of tempered glass (within 24" of doorways and when less than 60" above tub/shower floors), R308.4.
2. Note that tub/shower enclosures shall have nonabsorbent surfaces to 6' above the floor, R307.2. All glass enclosures shall be tempered, R308.4.5.
3. Locate and identify brace wall types and locations (include interior wall lines) along with the appropriate holdowns and nailing schedule, R602.10.

STRUCTURAL PLANS:

1. Provide complete roof and floor framing plans. Show size, spacing and span of all framing members, trusses, joists, rafters, beams, glue-lams, lintels, headers, ledgers and blocking.
3. Indicate how you are "canceling" window.
4. Note or detail trimmers, headers and framing anchors (show sizes) at framed door and window openings, both new and relocated.
5. Detail all brace wall connections from the foundation to the roof plywood.
6. Locate and identify brace wall panel materials (min 3/8" OSB) and locations along with the appropriate nailing schedule (8d @ 6" o/c edge & @12" o/c field), R602.10.6.
7. Provide a complete braced panel layout showing panels at the ends (within 12.5') of all wall lines and additional panels centered at least every 25' between, Table R602.10.1. All exterior wall lines shall be braced and parallel interior wall lines shall be braced at intervals not exceeding 35' from exterior wall lines, R602.10.1.1
8.Indicate method of attaching ridge beams together.
SECTIONS - DETAILS - MISC. NOTES:

1. Provide a header schedule consistent with Table 502.5(1).
2. Ceiling gypsum board shall be either 5/8" or ½" sag resistant when applied to 24" o/c

PLUMBING PLANS:

1. The City of Tucson has adopted the 2003 Uniform Plumbing Code with state amendments (ARIZONA STATE PLUMBING CODE). All plans must reference this code.
2. Provide the length of gas line (total developed length) from meter to the most remote appliance on the system and size the supply pipe for the connected demand, UPC 1217.2.
3. Show plumbing vents (VTR) within acceptable distances from traps (maximum 6' for water closets), UPC Table 10-1.

ELECTRICAL PLANS:

1. Note on plan that all electrical work shall comply with 2003 IRC chapters 33 - 42.
2. Note the location, type and amperage of the panel. Note the grounding and bonding method. Metallic gas lines must be bonded and shall not be used as the primary grounding method, E3508.
3. Designate the location and circuit of each light fixture, receptacle, and switch. Provide a panel schedule noting circuit number and breaker & wire size along with a general description.
4. Indicate an exterior outlet at grade level located at both the front and back of the dwelling, E3801.7. These outlets shall be GFCI protected E3802.3.
5. Note that all smoke detectors must be interconnected with a power source from the building wiring, and shall be equipped with battery backup. When ceiling finish materials are removed in existing construction, existing bedrooms shall be in compliance. When ceiling finish materials are not removed, existing bedrooms shall be equipped with battery operated smoke detectors, R313.1.1.
6. An arc-fault circuit interrupter shall protect bedroom outlets including receptacles, lights and smoke detectors, E3802.11.
7. Show location of main panel and sub panel, method and sizing of conductors to original panel location, panel schedule and load calculations.





If you have any questions, please contact your assigned plans examiner Daniel Rusch at 791-5550, extension 1113.