Permit Number: T06CM00991
Parcel: 131010460

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T06CM00991
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/17/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied If the existing restrooms have not been permitted, show how the fixtures have been plumbed.
02/17/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Show how the common ventilation has been adjusted per Section 403.3.2, IMC 2003.
2. Clarify the nature of the unit serving the garage bay.
3. Show how recirculation of the air from the restrooms will be prevented. Reference Section 403.2, IMC 2003.
4. Show how the ductwork has been insulated.
5. Show the location and type of thermostat for the heat pump.
6. Show the make, model, and capacity of the heat pump.
7. Show that the roof is capable of supporting the heat pump.
03/13/2006 MARTIN BROWN FIRE REVIEW Approved
03/13/2006 GERRY KOZIOL WWM REVIEW Approved
03/13/2006 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Needs Review
03/13/2006 SPOWELL1 WATER REVIEW Needs Review
03/13/2006 HEATHER THRALL ZONING REVIEW Approved
03/13/2006 SPOWELL1 ELECTRICAL-COMMERCIAL REVIEW Needs Review
03/13/2006 SUZANNE BOHNET ENGINEERING REVIEW Approved