Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T06CM00990
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/17/2006 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | If the restrooms have not been permitted, show how the fixtures have been plumbed. |
| 02/17/2006 | ROBERT SHERRY | WATER | REVIEW | Denied | Provide backflow protection for the water service. |
| 02/17/2006 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Show how the condensate is handled. 2. Clarify the nature of the unit serving the garage bay. 3. Show how recirculation of the air from the restrooms will be prevented. Reference Section 403.2, IMC 2003. 4. Show how the ductwork has been insulated. 5. Show the location and type of thermostat for the heat pump. 6. Show the make, model, and capacity of the heat pump. 7. Show that the roof is capable of supporting the heat pump. 8. Show how the condensate is handled. |
| 03/13/2006 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 03/13/2006 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 03/13/2006 | CHRISTY FOREMAN | BUILDING-COMMERCIAL | REVIEW | Needs Review | |
| 03/13/2006 | HEATHER THRALL | ZONING | REVIEW | Approved | |
| 03/13/2006 | SPOWELL1 | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review | |
| 03/13/2006 | SUZANNE BOHNET | ENGINEERING | REVIEW | Approved |