Permit Number: T06CM00977
Parcel: 121060100

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T06CM00977
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/09/2007 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Approved
02/14/2007 SUZANNE BOHNET ENGINEERING REVIEW Approved
02/26/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Third request. Indicate the location of the backflow preventer for the irrigation system and the point of connection to the domestic water system. Reference Section 103.2.3, UPC 2003.
2. Clarify the number of downspouts for the gutter and show that the size and slope of the gutter conforms to the size required by Table 11-3, UPC 2003 for the maximum projected roof area. [Provide location and sizing information for the new gutter and downspouts. Reference Section 1106.0, UPC 2003.]
02/26/2007 ROBERT SHERRY WATER REVIEW Denied Third request. Show the location and size of the reduced pressure backflow preventer for the site. Reference Section 103.2.3, UPC 2003.
03/12/2007 MICHAEL ST. PAUL ZONING REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
03/16/2007 FSANCHE1 OUT TO CUSTOMER Completed
03/16/2007 SUE REEVES REJECT SHELF Completed