Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T06CM00977
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/02/2007 | MICHAEL ST. PAUL | ZONING | REVIEW | Denied | See site plan comments. |
| 01/02/2007 | BETSY COTTLE | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 01/17/2007 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Second request. Indicate the location of the backflow preventer for the irrigation system and the point of connection to the domestic water system. Reference Section 103.2.3, UPC 2003. 2. Clarify the number of downspouts for the gutter and show that the size and slope of the gutter conforms to the size required by Table 11-3, UPC 2003 for the maximum projected roof area. [Provide location and sizing information for the new gutter and downspouts. Reference Section 1106.0, UPC 2003.] |
| 01/17/2007 | ROBERT SHERRY | WATER | REVIEW | Denied | Show the location and size of the reduced pressure backflow preventer for the site. Reference Section 103.2.3, UPC 2003. |
| 01/29/2007 | SUZANNE BOHNET | ENGINEERING | REVIEW | Denied | Building plans cannot be approved until the Site Plan is approved. |
| 12/22/2006 | CHRISTY FOREMAN | BUILDING-COMMERCIAL | REVIEW | Denied | PERMIT SHALL NOT BE ISSUED AND APPROVED UNTIL SITE PLAN HAS BEEN APPROVED. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 01/30/2007 | DELMA ROBEY | APPROVAL SHELF | Completed |
| 01/30/2007 | DELMA ROBEY | OUT TO CUSTOMER | Completed |
| 01/30/2007 | DELMA ROBEY | REJECT SHELF | Completed |