Permit Number: T06CM00977
Parcel: 121060100

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T06CM00977
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/02/2007 MICHAEL ST. PAUL ZONING REVIEW Denied See site plan comments.
01/02/2007 BETSY COTTLE COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
01/17/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Second request. Indicate the location of the backflow preventer for the irrigation system and the point of connection to the domestic water system. Reference Section 103.2.3, UPC 2003.
2. Clarify the number of downspouts for the gutter and show that the size and slope of the gutter conforms to the size required by Table 11-3, UPC 2003 for the maximum projected roof area. [Provide location and sizing information for the new gutter and downspouts. Reference Section 1106.0, UPC 2003.]
01/17/2007 ROBERT SHERRY WATER REVIEW Denied Show the location and size of the reduced pressure backflow preventer for the site. Reference Section 103.2.3, UPC 2003.
01/29/2007 SUZANNE BOHNET ENGINEERING REVIEW Denied Building plans cannot be approved until the Site Plan is approved.
12/22/2006 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Denied PERMIT SHALL NOT BE ISSUED AND APPROVED UNTIL SITE PLAN HAS BEEN APPROVED.

Final Status

Task End Date Reviewer's Name Type of Review Description
01/30/2007 DELMA ROBEY APPROVAL SHELF Completed
01/30/2007 DELMA ROBEY OUT TO CUSTOMER Completed
01/30/2007 DELMA ROBEY REJECT SHELF Completed