Permit Number: T06CM00977
Parcel: 121060100

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T06CM00977
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/03/2006 MARTIN BROWN FIRE REVIEW Approved
03/08/2006 GERRY KOZIOL WWM REVIEW Approved
03/14/2006 RAUL PALMA BUILDING-COMMERCIAL REVIEW Denied City of Tucson, Development Services
BUILDING AND STRUCTURAL COMMENTS

3/14/06

1) Specify use of covered area. 39'6"x24'(high roofed area)
2) State on plans that all new footings to extend 18" below natural soil minimum.
3) Sheet 7A ( cantilevered retaining wall sheet) under soil data is specified 1995 psf
and on sheet 1 of calcs and on plans it specifies 1500 psf. So that being the case
the soil pressure under the retaining wall footing is being exceeded.




City of Tucson, Development Services
BUILDING AND STRUCTURAL COMMENTS

3/14/06

1) Specify use of covered area. 39'6"x24'(high roofed area)
2) State on plans that all new footings to extend 18" below natural soil minimum.
3) Sheet 7A ( cantilevered retaining wall sheet) under soil data is specified 1995 psf
and on sheet 1 of calcs and on plans it specifies 1500 psf. So that being the case
the soil pressure under the retaining wall footing is being exceeded.
03/16/2006 SUZANNE BOHNET ENGINEERING REVIEW Denied Building plans cannot be approved until Site Plan is approved.
03/21/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Indicate the location of the backflow preventer for the irrigation system and the point of connection to the domestic water system. Reference Section 103.2.3, UPC 2003.
2. Provide location and sizing information for the new gutter and downspouts. Reference Section 1106.0, UPC 2003.
03/21/2006 ROBERT SHERRY WATER REVIEW Denied Show the location and size of the water meter and the reduced pressure backflow preventer for the site. Reference Section 103.2.3, UPC 2003.
03/21/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
03/27/2006 BOB SUBA ELECTRICAL-COMMERCIAL REVIEW Approved
05/11/2006 MICHAEL ST. PAUL ZONING REVIEW Denied Site plan approval required.

Final Status

Task End Date Reviewer's Name Type of Review Description
05/15/2006 AMERY KLAPPERT OUT TO CUSTOMER Completed
05/15/2006 SUE REEVES REJECT SHELF Completed