Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T06CM00967
Parcel: 13323164A

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T06CM00967
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/21/2006 BOB SUBA ELECTRICAL-COMMERCIAL REVIEW Denied See attached set of electrical permit requirements.Please make necessary changes-additions to the elec. plans.
03/07/2006 DOUG LAAKSO BUILDING-COMMERCIAL REVIEW Denied ..T06CM00967..7150 E SPEEDWAY BLVD..DGL..1ST REVIEW..3/7/06..
S1. SHOW WHERE 20% OF PROJECT VALUATION IS SPENT ON BRINGING ACCESSIBILITY OF THE SITE AND OVERALL BUILDING INTO COMPLIANCE WITH THE 2003 IBC PER SEC 11 AND 34 AND ANSI A117.1-2003 ED.

S2. CLARIFY CONFORMANCE OF THIS SPACE WITH IBC SECTIONS 11 AND 34 AND ANSI A117.1-2003 ED, WITH REGARD TO FIXTURE LOCATIONS, HEIGHT, ETC.

S3. SHOW ON DRAWINGS ATTACHMENT OF PARTITIONS TO FLOOR SLAB, INCLUDING FASTENER TYPE, SIZE AND SPACING.

S4. RESOLVE EXPIRED PERMITS :
1. T00CM00767
2. T01BU02315
3. T01CM01990
4. T03CM04884
PRIOR TO ISSUANCE OF THIS BUILDING PERMIT.

Questions? Call Douglas Laakso Structural Plans Examiner for the City of Tucson Development Services Department at (520) 791-5550 x1111.
03/20/2006 ROBERT SHERRY WATER REVIEW Approved
03/20/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide information to show how the proposed water heater is to be supported from the building structure. Reference Section 314.5, UPC 2003.
2. Provide cleanouts for the new sinks located in Exam #1, Exam #2, and the Contact room. Reference Section 707.4, UPC 2003.
3. Provide information to show that the specified floor drain can act as an indirect receptor for the T&P relief without splashing or flooding. Reference Section 804.1, UPC 2003.
4. Provide a vent for the new floor drain. FD-1. Reference Section 901.0
03/20/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide information to show that the capacity of EF-11 provides adequate ventilation for the pharmacy restroom. Reference Section 403.2.1(3) and Table 403.3, IMC 2003.
2. The minimum insulation for ducts located in unconditioned spaces within the building envelope is R-5 (installed). Reference Section 803.2.8, IECC 2003.

Final Status

Task End Date Reviewer's Name Type of Review Description
04/06/2006 DELMA ROBEY OUT TO CUSTOMER Completed
04/06/2006 SUE REEVES REJECT SHELF Completed