Permit Number: T06CM00944
Parcel: 11704311A

Address:
522 N 4TH AV

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T06CM00944
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/16/2006 MARTIN BROWN FIRE REVIEW Approved
02/16/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
02/16/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T06CM00944 2/16/06

1. Minimum font size is 1/8".
2. Fault calculations show as 63402A available at Panel LPC. But this panel is only rated at 10,000AIC. Please clarify, and note that the calc for this panel may be based on the 42,000A available at SES. Distance to Panel ATM appears to be 175', not 220 as used in the calculation.
3. If new lighting is intended for exterior application, please demonstrate compliance with the Tucson Lighting Code, http://www.tucsonaz.gov/dsd/Codes___Ordinances/Tucson_Lighting_Code.pdf.
02/16/2006 ROBERT SHERRY WATER REVIEW Passed
02/16/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
02/17/2006 JOSE ORTIZ ENGINEERING REVIEW Approved
02/17/2006 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Approved
02/28/2006 GBONILL1 WWM REVIEW Needs Review
02/28/2006 GBONILL1 ZONING REVIEW Needs Review