Permit Number: T06CM00943
Parcel: 11921053F

Address:
1440 W AJO WY

Review Status: Completed

Review Details: RESUBMITTAL - SITE ALL

Permit Number - T06CM00943
Review Name: RESUBMITTAL - SITE ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/14/2006 HEATHER THRALL ZONING REVIEW Approved
07/14/2006 HEATHER THRALL ZONING HC SITE REVIEW Approved
08/02/2006 PATRICIA GILBERT ENGINEERING REVIEW Denied DATE: August 2, 2006
ACTIVITY NUMBER: T06CM00943
PROJECT NAME: LaCasita Day Care
PROJECT ADDRESS: 1412 West Ajo Way
PROJECT REVIEWER: Patricia Gilbert, Engineering Associate

The following items must be revised or added to the site plan. Please include a response letter with the next submittal that states how all comments have been addressed.

RESUBMITTAL REQUIRED: SITE PLAN

APPROVED: DRAINAGE REPORT


1. The maximum back distance is 40' for the solid waste vehicle. The back distance indicated on the plan shows the solid waste backing up more than 40'. Be advised that when solid waste vehicle maneuverability does not meet Development Standard 6-01 a Development Standard Modification Request is required. Please contact Patricia Gehlen, Community Design Review Committee (CDRC) Manager for DSMR submittal criteria. Revise the plan or seek assistance with a DSMR.

The above comment is from the first review. Unfortunately the correction made on the site plan is not a sufficient correction. The back up distance now exceeds the maximum back up distance. Demonstrate maneuverability for the collection vehicle. Show the 36' inside radius and 50' outside radius per DS 6-01. Figure 1. Be advised the maximum back distance is 40' for the solid waste vehicle. Revise the site plan as necessary.

The above comments are from the previous reviews. The request has been made to show (draw) the 36' inside radius and 50' outside radius on the plan in effort to show the maneuverability has been met per DS 6-01, Figure 1. This has not been shown on the plan. Draw on the site plan the 36' inside radius and 50' outside radius. Demonstrate on the plan the solid waste vehicle does not obstruct parking spaces.

Final Status

Task End Date Reviewer's Name Type of Review Description
08/07/2006 CINDY AGUILAR OUT TO CUSTOMER Completed
08/07/2006 SUE REEVES REJECT SHELF Completed